Bryant 580J manual Cooling Capacities, Stagecooling, Tons

Models: 580J

1 94
Download 94 pages 40.55 Kb
Page 51
Image 51
Table 31 – COOLING CAPACITIES

Table 31 – COOLING CAPACITIES

2-STAGE COOLING

 

 

 

 

12.5 TONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

580J14 COOLING CAPACITIES, UNIT WITH PERFECT HUMIDITY SYSTEM IN SUBCOOLING MODE

 

 

 

 

 

 

 

 

 

AIR ENTERING EVAPORATOR --- CFM

 

 

 

 

 

TEMP (F) AIR ENT

 

3750/0.02

 

 

 

 

5000/0.06

 

 

 

 

6250/0.05

 

 

CONDENSER (Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Entering Evaporator --- Ewb (F)

 

 

 

 

 

 

 

 

 

72

 

67

 

62

 

72

 

67

 

62

 

72

 

67

 

62

 

 

TC

183.66

 

166.86

 

151.43

 

194.90

 

177.83

 

162.05

 

201.97

 

184.84

 

170.53

75

 

SHC

79.39

 

100.52

 

121.91

 

91.70

 

119.42

 

147.05

 

102.94

 

137.00

 

166.71

 

 

kW

9.82

 

9.63

 

9.46

 

9.58

 

9.76

 

9.96

 

10.04

 

9.84

 

9.67

 

 

TC

172.71

 

156.78

 

142.09

 

183.32

 

167.13

 

152.17

 

189.98

 

173.73

 

160.25

85

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHC

69.03

 

90.92

 

112.95

 

80.69

 

109.17

 

137.51

 

91.49

 

126.33

 

156.65

 

 

kW

10.82

 

10.63

 

10.45

 

10.57

 

10.76

 

10.96

 

11.04

 

10.84

 

10.67

 

 

TC

161.37

 

146.24

 

132.38

 

171.36

 

156.04

 

141.86

 

177.62

 

162.22

 

149.50

95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHC

58.44

 

81.04

 

103.77

 

69.42

 

98.67

 

127.71

 

79.83

 

115.45

 

146.15

 

 

kW

11.92

 

11.73

 

11.56

 

11.68

 

11.86

 

12.05

 

12.14

 

11.93

 

11.77

 

 

TC

149.57

 

135.32

 

122.21

 

158.89

 

144.45

 

131.10

 

164.74

 

150.27

 

138.35

105

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHC

47.57

 

70.92

 

94.32

 

57.85

 

87.91

 

117.61

 

67.79

 

104.26

 

135.30

 

 

kW

13.12

 

12.94

 

12.77

 

12.89

 

13.06

 

13.24

 

13.32

 

13.13

 

12.97

 

 

TC

137.22

 

123.88

 

111.55

 

145.85

 

132.33

 

119.84

 

151.27

 

137.71

 

126.67

115

 

SHC

36.31

 

60.47

 

84.57

 

45.87

 

76.77

 

107.19

 

55.34

 

92.66

 

123.98

 

 

kW

14.41

 

14.25

 

14.10

 

14.20

 

14.35

 

14.53

 

14.59

 

14.42

 

14.28

 

 

 

 

580J14 COOLING CAPACITIES, UNIT WITH PERFECT HUMIDITY SYSTEM IN HOT GAS REHEAT MODE

 

 

 

 

 

 

 

 

 

AIR ENTERING EVAPORATOR --- Ewb (F)

 

 

 

 

 

 

 

 

 

 

75 Dry Bulb

 

 

 

 

75 Dry Bulb

 

 

 

 

75 Dry Bulb

 

TEMP (F)AIR ENT

 

62.5 Wet Bulb

 

 

 

64 Wet Bulb

 

 

 

65.3 Wet Bulb

 

CONDENSER(Edb)

 

(50% Relative)

 

 

 

(56% Relative)

 

 

 

(60% Relative)

 

 

 

 

 

 

 

 

 

 

Air Entering Evaporator --- Cfm

 

 

 

 

 

 

 

 

 

3750

5000

 

6250

3750

5000

 

6250

 

3750

5000

 

6250

 

 

TC

52.42

45.88

 

36.99

62.64

58.07

 

51.07

 

71.56

68.64

 

63.23

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHC

--- 0.39

--- 0.54

 

--- 0.67

--- 0.31

--- 0.46

 

--- 0.58

 

--- 0.26

--- 0.40

 

--- 0.52

 

 

kW

9.65

9.39

 

9.07

9.97

9.77

 

9.50

 

10.25

10.11

 

9.89

 

 

TC

53.45

46.63

 

36.10

63.77

59.11

 

51.87

 

72.76

69.80

 

64.31

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHC

0.59

0.44

 

0.30

0.67

0.52

 

0.40

 

0.72

0.58

 

0.47

 

 

kW

9.09

8.83

 

8.49

9.39

9.20

 

8.94

 

9.67

9.53

 

9.32

 

 

TC

54.33

46.91

 

37.58

64.77

60.01

 

52.30

 

73.80

70.80

 

65.24

70

 

SHC

1.56

1.41

 

1.29

1.64

1.50

 

1.38

 

1.70

1.56

 

1.45

 

 

kW

8.81

8.53

 

8.62

9.15

8.94

 

8.65

 

9.46

9.31

 

9.08

 

 

TC

55.47

49.48

 

40.48

66.62

62.07

 

54.88

 

75.68

72.76

 

67.28

60

 

SHC

3.50

3.38

 

3.27

3.59

3.47

 

3.36

 

3.65

3.52

 

3.42

 

 

kW

8.36

8.84

 

8.98

9.88

9.56

 

9.10

 

9.83

9.64

 

9.31

 

 

TC

58.33

51.72

 

42.81

68.72

63.93

 

55.84

 

77.74

74.77

 

69.24

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHC

5.47

5.35

 

5.24

5.54

5.43

 

5.32

 

5.60

5.49

 

5.39

 

 

kW

8.98

9.25

 

9.43

9.33

8.97

 

8.73

 

9.55

9.33

 

9.70

 

 

TC

60.33

53.69

 

46.89

70.67

65.93

 

49.83

 

79.46

76.62

 

71.24

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHC

7.42

7.31

 

7.22

7.49

7.39

 

7.23

 

7.55

7.45

 

7.37

 

 

kW

9.16

9.88

 

9.06

9.50

9.05

 

9.47

 

10.31

10.00

 

9.48

NOTE: Perfect Humidity only available on 2---stage RTPF models.

LEGEND

 

NOTES:

 

 

Edb

---

Entering Dry--- Bulb

1. Direct interpolation is permissible. Do not extrapolate.

Ewb

---

Entering Wet--- Bulb

2. The following formulas may be used:

kW

---

Compressor Motor Power Input

 

sensible capacity (Btuh)

 

Idb

---

Leaving Dry--- Bulb

tldb = tedb

1.10 x cfm

Iwb

---

Leaving Wet--- Bulb

tlwb = Wet--- bulb temperature corresponding to enthalpy of air

SHC ---

Sensible Heat Capacity (1000 Btuh) Gross

leaving evaporator coil (hlwb)

TC

---

Total Capacity (1000 Btuh) Gross

 

total capacity (Btuh)

 

 

 

 

hlwb = hewb

 

 

 

4.5 x cfm

Where: hewb = Enthalpy of air entering evaporator coil

580J

51

Page 51
Image 51