580J
FAN PERFORMANCE (cont.)
Table 38 – 580J**05 |
|
| 1 PHASE |
| 4 TON HORIZONTAL SUPPLY | ||||||
|
|
|
|
|
|
|
|
|
| ||
|
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) |
|
|
| ||||
CFM |
| 0.2 |
| 0.4 | 0.6 |
| 0.8 |
|
| 1.0 | |
RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | ||
| |||||||||||
|
| Standard Static Option |
|
| Medium Static Option |
|
| ||||
1200 | 643 | 0.23 | 762 | 0.34 | 859 | 0.46 | 944 | 0.58 | 1020 | 0.71 | |
1300 | 675 | 0.28 | 790 | 0.40 | 886 | 0.52 | 969 | 0.65 | 1044 | 0.78 | |
1400 | 707 | 0.33 | 819 | 0.45 | 913 | 0.58 | 996 | 0.72 | 1070 | 0.86 | |
1500 | 740 | 0.38 | 849 | 0.52 | 941 | 0.66 | 1023 | 0.80 | 1096 | 0.95 | |
1600 | 773 | 0.45 |
|
| 970 | 0.73 | 1050 | 0.88 | 1123 | 1.04 | |
879 | 0.59 | ||||||||||
1700 | 807 | 0.52 | 910 | 0.67 | 999 | 0.82 | 1078 | 0.98 | 1150 | 1.14 | |
1800 | 841 | 0.59 | 942 | 0.75 | 1029 | 0.91 | 1106 | 1.08 |
|
| |
1177 | 1.25 | ||||||||||
1900 | 875 | 0.68 | 974 | 0.85 | 1059 | 1.02 | 1135 | 1.19 | 1205 | 1.37 | |
2000 | 910 | 0.77 | 1006 | 0.95 | 1090 | 1.13 | 1165 | 1.31 | 1234 | 1.49 | |
|
|
|
|
|
|
|
|
| |||
|
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) |
|
|
| ||||
CFM |
| 1.2 |
| 1.4 | 1.6 |
| 1.8 |
|
| 2.0 | |
RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | ||
| |||||||||||
|
| Medium Static Option |
|
|
| Field Supplied Drive1 |
|
| |||
1200 | 1089 | 0.84 | 1153 | 0.98 | 1213 | 1.12 | |||||
1300 | 1113 | 0.92 | 1177 | 1.06 | |||||||
1400 | 1138 | 1.01 | 1201 | 1.15 | |||||||
1500 | 1163 | 1.10 | |||||||||
1600 |
|
| |||||||||
1189 | 1.20 | ||||||||||
1700 | |||||||||||
1800 | |||||||||||
1900 | |||||||||||
2000 | |||||||||||
|
|
|
|
|
|
|
|
| |||
NOTE: For more information, see General Fan Performance Notes. |
|
|
|
|
| ||||||
Boldface indicates field supplied drive is required. |
|
|
|
|
|
| |||||
1. Recommend using field supplied motor pulley (part no. KR11HY161) and belt (part no. KR30AE035). |
|
|
|
Table 39 – 580J**05 |
|
| 1 PHASE |
|
| 4 TON VERTICAL SUPPLY | |||||
|
|
|
|
|
|
|
|
|
| ||
|
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) |
|
|
| ||||
CFM |
| 0.2 |
| 0.4 | 0.6 |
| 0.8 |
|
| 1.0 | |
RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | ||
| |||||||||||
|
| Standard Static Option |
|
| Medium Static Option |
|
| ||||
1200 | 666 | 0.26 | 778 | 0.37 | 871 | 0.47 | 952 | 0.57 | 1025 | 0.67 | |
1300 | 701 | 0.31 | 810 | 0.43 | 901 | 0.54 | 981 | 0.65 | 1053 | 0.76 | |
1400 | 737 | 0.36 | 842 | 0.49 | 931 | 0.62 | 1010 | 0.74 | 1081 | 0.86 | |
1500 | 773 | 0.42 | 875 | 0.57 | 963 | 0.70 | 1040 | 0.84 | 1110 | 0.96 | |
1600 | 810 | 0.49 | 909 | 0.65 | 994 | 0.79 | 1070 | 0.94 | 1140 | 1.08 | |
1700 | 847 | 0.57 | 943 | 0.73 | 1027 | 0.89 | 1101 | 1.05 | 1170 | 1.20 | |
1800 |
|
| 978 | 0.83 | 1060 | 1.00 | 1133 | 1.16 |
|
| |
885 | 0.66 | 1200 | 1.32 | ||||||||
1900 | 923 | 0.75 | 1014 | 0.94 | 1093 | 1.11 | 1165 | 1.29 | 1231 | 1.46 | |
2000 | 962 | 0.85 | 1049 | 1.05 | 1127 | 1.24 | 1198 | 1.42 | 1263 | 1.61 | |
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| ||||
|
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) |
|
|
| ||||
CFM |
| 1.2 |
| 1.4 | 1.6 |
| 1.8 |
|
| 2.0 | |
RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | ||
| |||||||||||
|
| Medium Static Option |
|
|
| Field Supplied Drive1 |
|
| |||
1200 | 1093 | 0.77 | 1155 | 0.87 | 1213 | 0.96 | 1268 | 1.05 | 1321 | 1.14 | |
1300 | 1119 | 0.87 | 1181 | 0.98 | 1239 | 1.08 | 1294 | 1.18 | |||
1400 | 1147 | 0.98 | 1208 | 1.09 | |||||||
1500 | 1175 | 1.09 | |||||||||
1600 |
|
| |||||||||
1700 | |||||||||||
1800 | |||||||||||
1900 | |||||||||||
2000 | |||||||||||
|
|
|
|
|
|
|
|
|
|
|
NOTE: For more information, see General Fan Performance Notes. Boldface indicates field supplied drive is required.
1. Recommend using field supplied motor pulley (part no. KR11HY161) and belt (part no. KR30AE035).