1.Normal Dehumidify Operation
When normal dehumidify is selected, the compressor will not turn on without a cooling demand. If dehumidify demand exists while cooling, dry contact will also be active (24VAC removed). This output commands
2.Cool to Dehumidify
The cool to dehumidify selection tells the system to operate the compres- sor, within limits, when there is a dehumidify demand even if there is no cooling demand. The limits are that the system may overcool up to 3_F, but no more, while attempting to satisfy a dehumidify demand. Within this 3_F range, there is an additional balance between overcooling and humidity satisfaction. When overcooling must occur, the dehumidify set- point is adjusted upward by 2% per degree of overcooling. For example, a cooling setpoint of 76_F and a dehumidify setpoint of 60% is equiva- lent to a cooling setpoint of 75_F and a dehumidify setpoint of 62%. This dehumidify setpoint change is internal to the Thermidistat Control and is not shown on the display.
46