Figure 36: Burner Adapter Plate Options
Power Flame (‘C’ Series) Burner Adapter Plate
Boiler Model | Part No. | I.D. | ‘A’ | ‘B’ |
|
| No. |
|
|
MPC4 thru MPC7 | 602263401 | 40 | ||
MPC8 thru MPC14 | 602263411 | 41 | 9 | 12 |
MPC15 thru MPC18 | 602263421 | 42 |
Power Flame (‘JR’ Series) Burner Adapter Plate
Boiler Model | Part No. | I.D. | ‘A’ | ‘B’ |
|
| No. |
|
|
MPC4 thru MPC7 | 602263451 | 45 | ||
MPC8 thru MPC11 | 602263461 | 46 |
Beckett (‘CF’ Series) Burner Adapter Plate
Boiler Model | Part No. | I.D. | ‘A’ | ‘B’ |
|
| No. |
|
|
MPC4 thru MPC7 | 602263001 | 00 | 10 | |
MPC8 thru MPC15 | 602263011 | 01 | 10 | |
MPC16 thru MPC18 | 602263021 | 02 | 11 | |
Beckett (‘CG’ Series) Burner Adapter Plate |
| |||
Boiler Model | Part No. | I.D. | ‘A’ | ‘B’ |
|
| No. |
|
|
MPC4 and MPC5 | 602263031 | 03 | 5 | 10 |
MPC6 and MPC7 | 602263041 | 04 | 6 | 10 |
MPC8 thru MPC11 | 602263071 | 07 | 10 | |
MPC12 thru MPC18 | 602263081 | 08 | 11 |
1.In most cases the burner adapter plate carton for the specified burner will be provided by Burnham.
2.If adapter is provided by Burnham, open carton and remove contents. Apply four (4) small dabs of silastic on rear surface of adapter plate to temporarily hold gasket in place. Hold adapter plate in position against burner swing door, align holes and secure with four (4) 3/8” lock washers and 3/8” - 16 x 7/8” lg. cap screws.
3.If adapter is furnished with burner, follow manufacturer’s instructions using gasket material and hardware provided with burner.
4.USE A HOLE SAW OR KNIFE TO CUT BURNER SWING DOOR INSULATION TO MATCH HOLE SIZE ON BURNER ADAPTER PLATE. After cutting, remove any and all loose pieces of insulation which may become lodged or interfere with the head of the burner air tube after insertion.
5.Secure burner to adapter plate with four (4) ½” lock washers and four (4) ½” - 13 hex nuts provided.
CAUTION
Failure to properly fill all gaps between the insulation and burner blast tube may result in damage to the burner.
6.Confirm that hole in insulation fits snugly around burner blast tube. If hole is oversized, open burner swing door (with burner attached) to access burner blast tube. Use additional fiberglass rope gasket provided with burner to fill in any space between insulation and blast tube. If additional rope gasket is not provided with the burner, use 3/8” fiberglass rope rated for 2300°F (provided by others).
When finished, close burner swing door and secure hardware.
P.Connect Internal Control / Safety Circuit Wiring Harness to Burner Controls, see Figures 25 and 37. Also, refer to Burner Installation Manual and wiring diagrams provided with burner.
51