Burnham FM01FD00B manual Alternate MPC Minimum Piping Multiple Boiler Application

Models: FM01FD00B

1 108
Download 108 pages 28.47 Kb
Page 62
Image 62

62

NOTES: For Boiler pipe sizes, flow rates, pressure drops and other important information and notes, refer to Figure 50a.

Boiler Operating Requirements:

Minimum Return Water Temperature = 80°F

Maximum Delta T = 80°F

Minimum Supply Water Temperature = 130°F

Figure 50b: Alternate MPC Minimum Piping - Multiple Boiler Application