Burnham FM01FD00B manual Table XII Recommended Periodic Testing Check List

Models: FM01FD00B

1 108
Download 108 pages 28.47 Kb
Page 72
Image 72

Table XII: Recommended Periodic Testing Check List (continued)

Item

Frequency

Accomplished by

Remarks

 

 

 

 

High Limit Safety Control

Annually

Service Technician

Refer to instructions

 

 

 

 

Operating Control

Annually

Service Technician

Refer to instructions

 

 

 

 

Low Draft, Fan, Air

Monthly

Operator

Refer to burner instructions

Pressure, and Damper

 

 

 

Position Interlocks

 

 

 

 

 

 

 

High and Low Gas

Monthly

Operator

Refer to burner instructions

Pressure Interlocks

 

 

 

 

 

 

 

High and Low Oil

Monthly

Operator

Refer to burner instructions

Pressure Interlocks

 

 

 

 

 

 

 

High and Low Oil

Monthly

Operator

Refer to burner instructions

Temperature Interlocks

 

 

 

 

 

 

 

Fuel Valve Interlock

Annually

Service Technician

Refer to burner instructions

Switch

 

 

 

 

 

 

 

Purge Switch

Annually

Service Technician

Refer to burner instructions

 

 

 

 

Burner Position Interlock

Annually

Service Technician

Refer to burner instructions

 

 

 

 

Burner Rotary Cup

Annually

Service Technician

Refer to burner instructions

Interlock

 

 

 

 

 

 

 

Low Fire Start Interlock

Annually

Service Technician

Refer to burner instructions

 

 

 

 

Automatic Fuel

At least annually

Service Technician

Under supervision of gas utility

Changeover Control

 

 

 

(Dual Fuel)

 

 

 

 

 

 

 

Safety Relief Valve

As required

Operator

In accordance with procedure in Section

 

 

 

VI, ASME Boiler and Pressure Vessel

 

 

 

Code, Recommended Rules for Care

 

 

 

and Operation of Heating Boilers

 

 

 

 

Burner Components

Semiannually

Service Technician

Refer to burner instructions

Inspection

 

 

 

 

 

 

 

72

Page 72
Image 72
Burnham FM01FD00B manual Table XII Recommended Periodic Testing Check List