Explanation of Jumper Settings (continued)
ECON JUMPER SETTING
If the jumper for MISC2 or MISC3 is set to ECON, the corresponding MISC screw terminal on the backplate will be connected to an economizer.
ECONOMIZER OPERATION - If your HVAC unit is equipped with an economizer system, the thermostat will provide power to the MISC2 or MISC3 terminal of the thermostat when the thermostat is in an occupied time period. The MISC2 or MISC3 terminal will be
Y2 JUMPER SETTING
If the jumper for MISC1 is set to Y2 the MISC1 screw terminal on the backplate will control a second stage of cooling.
Y2 OPERATION - SECTION 13
Control up to two Cool stages.
The 2nd Stage of cool is turned on when:
(A) The 1st Stage has been on for the time required (step #27, page 13.6). It is adjustable from
And
(B) The temperature spread from the setpoint is equal to or greater than: the setpoint plus the deadband (step #24, page 13.5), plus the 2nd deadband (step #25, page 13.5). This 2nd deadband is adjustable from
21
| Cooling |
|
Deadband | Deadband |
|
db 1 | db 2 |
|
(adj. | (adj. |
|
Cool | 1st Stage | 2nd Stage |
Setpoint | turn on | turn on |
TEMPERATURE INCREASE