Use the following formula to determine the percent volt- age imbalance.
% Voltage Imbalance:
max voltage deviation from average voltage
= 100 x
average voltage EXAMPLE: Supply voltage is
AB =452 v
BC =464 v
AC =455 v
Average Voltage = | 452 +464 +455 | ||
3 | |||
| |||
= | 1371 |
| |
3 |
| ||
|
|
= 457
Determine maximum deviation from average voltage:
(AB) 457 −452 =5 v (BC) 464 −457 =7 v (AC) 457 −455 =2 v
Maximum deviation is 7 v. Determine percent voltage imbalance:
% Voltage Imbalance =100 x | 7 | |
457 | ||
=1.53% | ||
|
This amount of phase imbalance is satisfactory as it is be- low the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility com- pany immediately.
Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components.
FIELD CONTROL WIRING Ð Install a
Route thermostat cable or equivalent single leads of col- ored wire from subbase terminals through conduit in unit to
NOTE: For wire runs up to 50 ft, use no. 18 AWG (Ameri- can Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly con- nected at the thermostat and will require a junction box and splice at the thermostat.
Set heat anticipator settings as follows:
UNIT | VOLTAGE UNIT | W1 | W2 | |
48HJD015 | All | 1.20 | Ð | |
48HJD025, HJE015, | All | 1.20 | 0.60 | |
HJE017 | ||||
|
|
|
Settings may be changed slightly to provide a greater de- gree of comfort for a particular installation.
Refer to Accessory Remote Control Panel instructions if required.
Step 9 Ð Make Outdoor-Air Inlet Adjustments
MANUAL
Damper can be preset to admit up to 25% outdoor air into
OPTIONAL
Economizer Motor Control Module (See Fig.
Damper Vent Position Setting
1.Set fan switch at ON position (continuous fan operation) and close night switch if used.
2.Set system selector switch at OFF position.
3.Turn damper adjustment knob located on control module clockwise slowly until dampers assume desired vent po- sition. Do not manually operate economizer motor. Dam- age to motor will result.
NOTE: Refer to accessory installation instructions included with the
Step 10 Ð Install
NOTE: The hood top cover, upper and lower ®lter retain- ers, hood drain pan, baffle (017 and 025 only), and ®lter sup- port bracket are secured opposite the condenser end of the unit. The screens, hood side panels, remaining section of ®l- ter support bracket, seal strip, and hardware are in a package located inside the
1.Attach seal strip to upper ®lter retainer. See Fig. 21.
2.Assemble hood top cover, side panels, upper ®lter re- tainer, and drain pan (see Fig. 22).
3.Secure lower ®lter retainer and long portion of support bracket to unit. See Fig. 22. Leave screws loose on 017 and 025 units.
4.48HJ017,025 Units Only: Slide baffle behind lower ®lter retainer and tighten screws.
Fig. 15 Ð Field Control Thermostat Wiring
Fig. 16 Ð 25% Outdoor-Air Section Details
10