SERVICE AND REPLACEMENT (See Fig. 30) Ð The 48HJ017,025 units use a fan motor mounting system that features a
1.Remove the
2.Remove the center post (located between the evaporator fan and heating control access panels) and all screws securing it.
3.Loosen nuts on the two carriage bolts in the motor mount- ing base.
4.Using jacking bolt under motor base, raise motor to top of slide and remove belt. Secure motor in this position by tightening the nuts on the carriage bolts.
5.Remove the belt drive.
6.Remove jacking bolt and tapped jacking bolt plate.
7.Remove the 2 screws that secure the motor mounting plate to the motor support channel.
8.Remove the 3 screws from the end of the motor support channel that interfere with the motor slide path.
9.Slide out the motor and motor mounting plate.
10.Disconnect wiring connections and remove the 4 mount- ing bolts.
11.Remove the motor.
12.To install the new motor, reverse Steps
Belt Tension Adjustment Ð To adjust belt tension:
1.Loosen fan motor bolts.
2.a. 015 Units: Move motor mounting plate up or down for proper belt tension (1¤2 in. de¯ection with one ®nger).
b.017,025 Units: Turn motor jacking bolt to move mo- tor mounting plate up or down for proper belt tension (3¤8 in. de¯ection at midspan with one ®nger [9 lb force]).
3.Tighten nuts.
4.Adjust bolts and nut on mounting plate to secure motor in ®xed position.
Condenser-Fan Adjustment
48HJ015,017 UNITS (Fig. 31)
1.Shut off unit power supply.
2.Remove access panel(s) closest to the fan to be adjusted.
3.Loosen fan hub setscrews.
4.Adjust the fan height on the shaft using a straightedge placed across the fan ori®ce.
5.Tighten setscrews and replace panel(s).
6.Turn on unit power.
48HJ025 UNITS (Fig. 32)
1.Shut off unit power supply.
2.Remove fan
3.Adjust fan height on unit, using a straightedge placed across the fan ori®ce.
4.Tighten setscrews and replace rubber hubcap to prevent hub from rusting to motor shaft.
5.Fill hub recess with permagum if rubber hubcap is missing.
Economizer Adjustment Ð Refer to Tables 8 and 9 for economizer checkout procedures. Make certain the outdoor- air damper is fully closed and the
1. Turn on power to the unit.
2.Turn the thermostat fan switch to the ON position. The damper will go to the vent position.
3.Adjust the vent position with the minimum position ad- justment on the economizer motor control module. See Fig. 18.
4.Set the system selector switch to COOL position and set the cooling temperature selector to its lowest setting.
NOTE: The Cooling mode may also be simulated by removing the thermostat wires from terminals Y1 and Y2 and installing a jumper between terminals R and Y1. Refer to unit label diagram for terminal locations.
NOTE: A
Fig. 30 Ð 48HJ017,025 Evaporator-Fan
Motor Section
Fig. 31 Ð Condenser Fan Adjustment,
48HJ015,017
Fig. 32 Ð
48HJ025
20