Carrier 48HJ015-025 Ð Combustion Fan Housing Location, Ð Condensate Drain Details

Models: 48HJ015-025

1 32
Download 32 pages 31.84 Kb
Page 8
Image 8
Fig. 10 Ð Combustion Fan Housing Location

PRESSURE

SWITCH

COMBUSTION

FAN HOUSING

HEAT

EXCHANGER

SECTION

Fig. 10 Ð Combustion Fan Housing Location

Step 6 Ð Trap Condensate Drain Ð See Fig. 11 for drain location. One 3¤4-in. half coupling is provided inside unit evaporator section for condensate drain connec- tion. An 81¤2 in. x 3¤4-in. diameter and 2-in. x 3¤4-in. diameter pipe nipple, coupled to standard 3¤4-in. diameter elbows, pro- vides a straight path down through hole in unit base rail (see Fig. 12). A trap at least 4-in. deep must be used.

Step 7 Ð Install Gas Piping Ð Unit is equipped for use with natural gas. Installation must conform with local building codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1.

Install manual gas shutoff valve with a 1¤8-in. NPT pres- sure tap for test gage connection at unit. Field gas piping must include sediment trap and union. See Fig. 13.

Do not pressure test gas supply while connected to unit. Always disconnect union before servicing.

Natural gas pressure at unit gas connection must not be less than 5 in. wg or greater than 13.5 in. wg.

Size gas-supply piping for 0.5-in. wg maximum pressure drop. Do not use supply pipe smaller than unit gas connec- tion (3¤4-in. NPT).

8

3/4" FPT DRAIN

1-3/8"

CONNECTION

DRAIN HOLE

Fig. 11 Ð Condensate Drain Details

Fig. 12 Ð Condensate Drain Piping Details

Fig. 13 Ð Field Gas Piping

Page 8
Image 8
Carrier 48HJ015-025 Ð Combustion Fan Housing Location, Ð Condensate Drain Details, Ð Condensate Drain Piping Details