Table 5 Ð Fan Performance Data, 48HJ025 Units
| AIRFLOW |
|
|
|
|
|
|
| EXTERNAL STATIC PRESSURE (in. wg) |
|
|
|
|
|
|
|
| |||||||||
|
| 0.2 |
|
|
| 0.4 |
|
|
|
|
| 0.6 |
|
|
|
|
| 0.8 |
|
|
|
| 1.0 |
| ||
| (CFM) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
| Rpm | Watts | Bhp |
| Rpm |
| Watts |
| Bhp |
| Rpm |
| Watts |
| Bhp |
| Rpm |
| Watts |
| Bhp | Rpm |
| Watts | Bhp |
6000 | 800 | 1732 | 1.88 | 891 | 2047 | 2.22 | 975 |
| 2376 | 2.58 | 1055 |
| 2728 | 2.96 | 1133 |
| 3104 | 3.37 | ||||||||
6500 | 853 | 2134 | 2.32 | 939 | 2471 | 2.68 | 1018 |
| 2819 | 3.06 | 1094 |
| 3185 | 3.46 | 1167 |
| 3573 | 3.88 | ||||||||
7000 | 907 | 2596 | 2.82 | 989 | 2957 | 3.21 | 1064 |
| 3324 | 3.61 | 1136 |
| 3707 | 4.02 | 1205 |
| 4107 | 4.46 | ||||||||
7500 | 962 | 3123 | 3.39 | 1039 | 3507 | 3.81 | 1111 |
| 3895 | 4.23 | 1179 |
| 4295 | 4.66 | 1245 |
| 4710 | 5.11 | ||||||||
8000 | 1017 | 3717 | 4.04 | 1091 | 4126 | 4.48 | 1160 |
| 4536 | 4.93 | 1225 |
| 4954 | 5.38 | 1287 |
| 5386 | 5.85 | ||||||||
8500 | 1072 | 4385 | 4.76 | 1143 | 4818 | 5.23 | 1209 |
| 5250 | 5.70 | 1271 |
| 5688 | 6.18 | 1332 |
| 6137 | 6.66 | ||||||||
9000 | 1128 | 5129 | 5.57 | 1196 | 5587 | 6.07 | 1260 |
| 6042 | 6.56 | 1323 |
| 6501 | 7.06 | 1377 |
| 6968 | 7.57 | ||||||||
9500 | 1185 | 5955 | 6.47 | 1250 | 6437 | 6.99 | 1311 |
| 6915 | 7.51 | 1369 |
| 7395 | 8.03 | 1424 |
| 7881 | 8.56 | ||||||||
10000 | 1241 | 6865 | 7.45 | 1304 | 7372 | 8.00 | 1363 |
| 7873 | 8.65 | 1419 |
| 8376 | 9.09 | 1472 |
| 8882 | 9.64 | ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
| AIRFLOW |
|
|
|
|
|
|
| EXTERNAL STATIC PRESSURE (in. wg) |
|
|
|
|
|
|
|
| |||||||||
|
| 1.2 |
|
|
| 1.4 |
|
|
|
|
| 1.6 |
|
|
|
|
| 1.8 |
|
|
|
| 2.0 |
| ||
| (CFM) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
| Rpm | Watts | Bhp |
| Rpm |
| Watts |
| Bhp |
| Rpm |
| Watts |
| Bhp |
| Rpm |
| Watts |
| Bhp | Rpm |
| Watts | Bhp |
| 6000 | 1208 | 3504 | 3.80 |
| 1282 |
| 3926 |
| 4.26 |
| 1353 |
| 4368 |
| 4.74 |
| 1421 |
| 4826 |
| 5.24 | 1488 |
| 5299 | 5.75 |
6500 | 1239 | 3983 | 4.32 |
| 1308 |
| 4415 |
| 4.79 |
| 1376 |
| 4866 |
| 5.28 |
| 1442 |
| 5337 |
| 5.79 | 1507 |
| 5823 | 6.32 | |
7000 | 1273 | 4529 | 4.92 |
| 1339 |
| 4970 |
| 5.40 |
| 1403 |
| 5432 |
| 5.90 |
| 1467 |
| 5911 |
| 6.42 | 1520 |
| 6339 | 6.88 | |
7500 | 1309 | 5143 | 5.58 |
| 1372 |
| 5597 |
| 6.08 |
| 1434 |
| 6067 |
| 6.59 |
| 1494 |
| 6558 |
| 7.12 | 1548 |
| 7014 | 7.62 | |
8000 | 1349 | 5833 | 6.33 |
| 1409 |
| 6297 |
| 6.84 |
| 1467 |
| 6779 |
| 7.36 |
| 1529 |
| 7313 |
| 7.94 | Ð |
| Ð | Ð | |
8500 | 1390 | 6600 | 7.17 |
| 1447 |
| 7077 |
| 7.68 |
| 1504 |
| 7571 |
| 8.22 |
| Ð |
| Ð |
| Ð | Ð | Ð | Ð |
| |
9000 | 1433 | 7446 | 8.08 |
| 1488 |
| 7938 |
| 8.62 |
| Ð |
| Ð |
| Ð |
| Ð | Ð | Ð |
| Ð | Ð |
| Ð |
| |
9500 | 1478 | 8378 | 9.10 |
| Ð |
| Ð |
| Ð |
| Ð | Ð | Ð |
| Ð |
| Ð |
| Ð |
| Ð | Ð |
| Ð |
| |
| 10000 | 1524 | 9396 | 10.20 |
| Ð |
| Ð |
| Ð |
| Ð | Ð | Ð |
| Ð |
| Ð |
| Ð |
| Ð | Ð |
| Ð |
|
|
| LEGEND |
Bhp | Ð Brake Horsepower Input to Fan | |
FIOP | Ð | |
Watts | Ð | Input Watts to Motor |
NOTES:
1.Boldface indicates standard operating range.
2.All other numbers indicates
3.Factory shipped motor drive range is 1323 to 1579 rpm. Other rpms require a
4.Static pressure losses (i.e., economizer) must be added to exter- nal static pressure before entering Fan Performance table. See Table 7 for accessory/FIOP static pressure information.
5.Interpolation is permissible. Do not extrapolate.
6.Maximum continuous bhp is 10.2 for 208/230 and
Table 6 Ð Air Quantity Limits
UNIT 48HJ | MINIMUM CFM | MAXIMUM CFM |
015 | 3,750 | 6,250 |
017 | 4,500 | 7,500 |
025 | 6,000 | 10,000 |
|
|
|
Fig. 24 Ð Fan Performance Using Accessory
Power Exhaust
16