Carrier 48HJ015-025 Ð Make Electrical Connections, Ð Field Power Wiring Connections

Models: 48HJ015-025

1 32
Download 32 pages 31.84 Kb
Page 9
Image 9
Step 8 Ð Make Electrical Connections

Step 8 Ð Make Electrical Connections

FIELD POWER SUPPLY Ð Unit is factory wired for volt- age shown on unit nameplate.

When installing units, provide a disconnect per NEC (National Electrical Code) of adequate size (Table 2).

All ®eld wiring must comply with NEC and local requirements.

Route power and ground lines through control box end panel or unit basepan (see Fig. 4 and 5) to connections as shown on unit wiring diagram and Fig. 14.

The unit must be electrically grounded in accordance with local codes and NEC ANSI/NFPA 70 (National Fire Protection Association).

Field wiring must conform to temperature limitations for type ``T'' wire. All ®eld wiring must comply with NEC and local requirements.

Transformer no. 1 is wired for 230-v unit. If 208/230-v unit is to be run with 208-v power supply, the transformer must be rewired as follows:

1.Remove cap from red (208 v) wire.

2.Remove cap from orange (230 v) spliced wire.

3.Replace orange wire with red wire.

4.Recap both wires.

 

LEGEND

EQUIP

Ð Equipment

GND

Ð Ground

NEC

Ð National Electrical Code

TB

Ð Terminal Board

NOTE: Maximum wire size for TB1 is 2/0.

Fig. 14 Ð Field Power Wiring Connections

IMPORTANT: BE CERTAIN UNUSED WIRES ARE CAPPED. Failure to do so may damage the transformers.

Operating voltage to compressor must be within voltage range indicated on unit nameplate. On 3-phase units, volt- ages between phases must be balanced within 2%.

Table 2 Ð Electrical Data

 

NOMINAL

VOLTAGE

COMPRESSOR

 

 

 

OFM

 

 

 

IFM

 

POWER

COMBUSTION

POWER SUPPLY

DISCONNECT

UNIT

VOLTAGE

RANGE

No. 1

No. 2

 

 

 

 

 

 

 

 

 

 

 

EXHAUST

FAN MOTOR

 

 

 

 

SIZE

48HJ

(3 Ph,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Min

Max

RLA

LRA

RLA

LRA

Qty

 

FLA

LRA

 

Hp

FLA

LRA

FLA

LRA

FLA

 

MCA

 

MOCP*

FLA

 

LRA

 

60 Hz)

 

 

 

 

 

 

 

(ea)

 

(ea)

 

 

 

 

 

208/230

187

254

39.7

228

Ð

Ð

3

 

 

1.7

 

3.8

3.7

10.5/10.5

84.5/84.5

Ð

Ð

0.57

 

65/65

 

100/100

64/64

 

324/324

 

 

 

 

4.6

18.8

0.57

 

70/70

 

100/100

70/70

 

343/343

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

015

460

414

508

19.9

114

Ð

Ð

3

 

 

0.8

 

1.9

3.7

4.8

42.3

Ð

Ð

0.30

 

32

 

50

32

 

162

 

 

 

2.3

6.0

0.30

 

34

 

50

34

 

168

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

518

632

16.0

91

Ð

Ð

3

0.75

 

1.5

 

3

3.9

23.4

Ð

Ð

0.57

 

26

 

40

26

 

119

 

 

 

2.1

4.8

0.57

 

28

 

40

29

 

124

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230

187

254

28.2

160

28.2

160

3

 

1.7

 

24.8

5

15.8/15.8

105/91

Ð

Ð

0.57

 

84/84

 

110/100

90/90

 

499/485

 

 

 

4.6

18.8

0.57

 

89/89

 

110/110

95/95

 

518/504

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

017

460

414

508

14.1

80

14.1

80

3

 

0.8

 

10.8

5

7.9

46

Ð

Ð

0.30

 

42

 

50

45

 

238

 

 

2.3

6.0

0.30

 

44

 

50

47

 

244

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

518

632

11.3

64

11.3

64

3

 

0.75

 

8.4

 

5

6.0

37

Ð

Ð

0.57

 

34

 

40

36

 

190

 

 

 

 

2.1

4.8

0.57

 

36

 

45

39

 

195

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230

187

254

35.6

198

35.6

198

2

 

5.5

 

24.8

10

28.0/28.0

193/168

Ð

Ð

0.57

 

119/119

 

150/150

127/127

 

639/614

 

 

 

4.6

18.8

0.57

 

124/124

150/150

133/133

657/632

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

025

460

414

508

17.8

99

17.8

99

2

 

2.8

 

10.8

10

14.6

84

Ð

Ð

0.30

 

60

 

70

65

 

304

 

 

2.3

6.0

0.30

 

63

 

80

67

 

310

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

518

632

14.3

79

14.3

79

2

 

3.4

 

8.4

 

10

13.0

66

Ð

Ð

0.57

 

52

 

60

56

 

241

 

 

 

 

2.1

4.8

0.57

 

54

 

60

59

 

246

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLA

Ð

LEGEND

Full Load Amps

HACR

Ð Heating, Air Conditioning and Refrigeration

IFM

Ð Indoor (Evaporator) Fan Motor

LRA

Ð

Locked Rotor Amps

MCA

Ð Minimum Circuit Amps

MOCP

Ð Maximum Overcurrent Protection

NEC

Ð

National Electrical Code

OFM

Ð Outdoor (Condenser) Fan Motor

RLA

Ð

Rated Load Amps

*This is the maximum size permissible; smaller fuse size may be used where conditions permit.

NOTES: In compliance with NEC requirements for multimotor and combina- tion load equipment (refer to NEC Articles 430 and 440), the overcurrent pro- tective device for the unit shall be fuse or HACR breaker. The Canadian units may be fuse or circuit breaker.

9

Page 9
Image 9
Carrier 48HJ015-025 Ð Make Electrical Connections, Ð Field Power Wiring Connections, Ð Electrical Data