Table 3A Ð Fan Performance Data, 48HJ015, 208/230,
AIRFLOW |
|
|
|
|
| EXTERNAL STATIC PRESSURE (in. wg) |
|
|
|
|
|
| ||||
| 0.2 |
|
| 0.4 |
|
| 0.6 |
|
| 0.8 |
|
| 1.0 |
|
| |
(CFM) |
|
|
|
|
|
|
|
|
|
|
| |||||
| Rpm | Watts | Bhp | Rpm | Watts | Bhp | Rpm | Watts | Bhp | Rpm | Watts | Bhp | Rpm | Watts | Bhp | |
3750 | 741 | 510 | 0.58 | 854 | 715 | 0.82 | 952 | 921 | 1.05 | 1041 | 1130 | 1.29 | 1124 | 1344 |
| 1.53 |
4000 | 773 | 647 | 0.74 | 882 | 859 | 0.98 | 978 | 1071 | 1.22 | 1064 | 1285 | 1.46 | 1145 | 1502 |
| 1.71 |
4250 | 806 | 796 | 0.91 | 912 | 1015 | 1.16 | 1004 | 1233 | 1.40 | 1089 | 1452 | 1.65 | 1167 | 1674 |
| 1.91 |
4500 | 839 | 958 | 1.09 | 942 | 1183 | 1.35 | 1032 | 1407 | 1.60 | 1114 | 1632 | 1.86 | 1191 | 1859 |
| 2.12 |
4750 | 873 | 1134 | 1.29 | 972 | 1365 | 1.56 | 1060 | 1595 | 1.82 | 1140 | 1825 | 2.08 | 1215 | 2056 |
| 2.34 |
5000 | 908 | 1323 | 1.51 | 1003 | 1560 | 1.78 | 1089 | 1796 | 2.05 | 1167 | 2032 | 2.32 | 1241 | 2268 |
| 2.58 |
5250 | 942 | 1527 | 1.74 | 1035 | 1769 | 2.02 | 1118 | 2011 | 2.29 | 1195 | 2252 | 2.57 | 1267 | 2494 |
| 2.84 |
5500 | 978 | 1745 | 1.99 | 1067 | 1992 | 2.27 | 1148 | 2240 | 2.55 | 1223 | 2487 | 2.83 | 1293 | 2733 |
| 3.11 |
5750 | 1013 | 1978 | 2.25 | 1099 | 2230 | 2.54 | 1179 | 2484 | 2.83 | 1252 | 2736 | 3.12 | 1321 | 2988 |
| 3.40 |
6000 | 1049 | 2227 | 2.54 | 1132 | 2483 | 2.83 | 1210 | 2742 | 3.12 | 1282 | 2999 | 3.42 | 1349 | 3257 |
| 3.71 |
6250 | 1085 | 2491 | 2.84 | 1166 | 2751 | 3.13 | 1241 | 3015 | 3.44 | 1312 | 3279 | 3.74 | 1378 | 3541 |
| 4.03 |
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
AIRFLOW |
|
|
|
|
| EXTERNAL STATIC PRESSURE (in. wg) |
|
|
|
|
|
| ||||
| 1.2 |
|
| 1.4 |
|
| 1.6 |
|
| 1.8 |
|
| 2.0 |
|
| |
(CFM) |
|
|
|
|
|
|
|
|
|
|
| |||||
| Rpm | Watts | Bhp | Rpm | Watts | Bhp | Rpm | Watts | Bhp | Rpm | Watts | Bhp | Rpm | Watts | Bhp | |
3750 | 1203 | 1562 | 1.78 | 1277 | 1784 | 2.03 | 1349 | 2010 | 2.29 | 1417 | 2240 | 2.55 | 1483 | 2473 |
| 2.82 |
4000 | 1222 | 1724 | 1.96 | 1294 | 1950 | 2.22 | 1364 | 2180 | 2.48 | 1431 | 2413 | 2.75 | 1495 | 2650 |
| 3.02 |
4250 | 1242 | 1900 | 2.16 | 1313 | 2129 | 2.43 | 1381 | 2362 | 2.69 | 1446 | 2599 | 2.96 | 1509 | 2839 |
| 3.23 |
4500 | 1264 | 2089 | 2.38 | 1333 | 2322 | 2.65 | 1399 | 2558 | 2.91 | 1463 | 2799 | 3.19 | 1525 | 3042 |
| 3.47 |
4750 | 1286 | 2290 | 2.61 | 1354 | 2528 | 2.88 | 1419 | 2769 | 3.15 | 1482 | 3012 | 3.43 | 1542 | 3259 |
| 3.71 |
5000 | 1310 | 2507 | 2.86 | 1376 | 2748 | 3.13 | 1440 | 2992 | 3.41 | 1501 | 3240 | 3.69 | 1560 | 3489 |
| 3.98 |
5250 | 1335 | 2737 | 3.12 | 1399 | 2983 | 3.40 | 1461 | 3230 | 3.68 | 1522 | 3481 | 3.97 | Ð | Ð |
| Ð |
5500 | 1360 | 2981 | 3.40 | 1423 | 3231 | 3.68 | 1484 | 3483 | 3.97 | 1543 | 3737 | 4.26 | Ð | Ð |
| Ð |
5750 | 1386 | 3241 | 3.69 | 1448 | 3495 | 3.98 | 1508 | 3750 | 4.27 | Ð | Ð | Ð | Ð | Ð | Ð |
|
6000 | 1413 | 3514 | 4.00 | 1474 | 3773 | 4.30 | 1532 | 4032 | 4.59 | Ð | Ð | Ð | Ð | Ð | Ð |
|
6250 | 1440 | 3803 | 4.33 | 1500 | 4066 | 4.63 | 1558 | 4330 | 4.93 | Ð | Ð | Ð | Ð | Ð | Ð |
|
|
| LEGEND |
Bhp | Ð Brake Horsepower Input to Fan | |
FIOP | Ð | |
Watts | Ð | Input Watts to Motor |
NOTES:
1.Boldface indicates standard operating range.
2. indicates
3.All other numbers indicate
4.Factory shipped motor drive range is 1194 to 1526 rpm. Other rpms require a
5.Static pressure losses (i.e., economizer) must be added to exter- nal static pressure before entering Fan Performance table. See Table 7 for accessory/FIOP static pressure information.
6.Interpolation is permissible. Do not extrapolate.
7.Maximum continuous bhp is 4.25 and the maximum continuous watts are 3775. Extensive motor and drive testing on these units ensures that the full horsepower range of the motor can be uti- lized with con®dence. Using your fan motors up to the watts rating shown will not result in nuisance tripping or premature motor fail- ure. Unit warranty will not be affected.
13