Main Burners Ð For most applications, main burners are factory set and should require no adjustment. However, if burner adjustment is necessary:
1.Perform pilot adjustment.
2.Turn gas valve to ON position. Allow unit to operate at least 15 minutes with burner access panel in place.
3.Remove access panel.
4.Loosen primary air shutter (Fig. 37) and adjust to a mini- mum opening of 5¤8 inch.
5.Retighten primary air shutter and reinstall access panel.
To check ignition of main burners and fan switch opera- tion, move thermostat dial above and below room tempera- ture several times, pausing at least one minute between cycles.
MAIN BURNER REMOVAL
1.Shut off
2.Shut off power to unit.
3.Remove unit control box/gas valve access panel, burner section access panel, and center post (Fig. 4 and 5).
4.Disconnect pilot ignitor and pilot proving sensor leads at ICP, rollout switch leads at switch, and pilot tube gas con- nection(s) at the pilot ori®ce.
5.Disconnect gas connection(s) from between gas valve(s) and main burners.
6.Remove 2 screws securing burner assembly to base unit.
7.Slide burner assembly out of unit.
Filter Drier Ð Replace whenever refrigerant system is exposed to atmosphere.
Protective Devices
COMPRESSOR PROTECTION
Overcurrent Ð Each compressor has one manual reset, cali- brated trip, magnetic circuit breaker. Do not bypass connec- tions or increase the size of the circuit breaker to correct trouble. Determine the cause and correct it before resetting the breaker.
Overtemperature Ð Each compressor has an internal pro- tector to protect it against excessively high discharge gas temperatures.
Crankcase HeaterÐ Each compressor has a
in the crankcase when the compressor is idle. Since power for the crankcase heaters is drawn from the unit incoming power, main unit power must be on for the heaters to be energized.
IMPORTANT: After a prolonged shutdown or serv- ice job, energize the crankcase heaters for 24 hours before starting the compressors.
Compressor Lockout Ð If any of the safeties
HIGH- AND
FREEZE PROTECTION THERMOSTAT (FPT) Ð An FPT is located on the evaporator coil. It detects frost
Relief Devices Ð All units have relief devices to pro- tect against damage from excessive pressures (i.e., ®re). These devices protect the high and low side.
Control Circuit,
Replacement Parts Ð A complete list of replacement parts may be obtained from any Carrier distributor upon request.
23