START-UP
Use the following information and
Unit Preparation Ð Check that unit has been installed in accordance with these installation instructions and appli- cable codes.
Compressor Mounting Ð Loosen the compressor hold- down bolts until sidewise movement of the washer under each holddown bolt head can be obtained. Do not loosen completely as bolts are
Internal Wiring Ð Check all electrical connections in unit control boxes; tighten as required.
Refrigerant Service Ports and Valves Ð Each 48HJ unit has 2
Crankcase Heater Ð Crankcase heater is energized as long as there is power to the unit.
IMPORTANT: Unit power must be on for 24 hours prior to
Evaporator Fan Ð Fan belt and pulleys are factory in- stalled. See Tables 3A, 3B, 4, and 5 for Fan Performance Data. Remove tape from fan pulley and adjust pulleys on 48HJ015 units as required. See
Accessory
ment Ð Remove ®lter access panel. Check that outdoor- air damper is closed and
Economizer operation and adjustment are described in Base Unit Operation section on page 17; and Economizer Adjustment section on page 20.
NOTES:
1.Dimensions are in millimeters.
2.The 50DP900211 high static regain adapter accessory may be used to provide horizontal supply/return.
NOTE: The 50DP900211 horizontal supply/return adapter accessory improves 48HJ fan performance by increasing external static pres- sure by amount shown above.