6.Insert the hood divider between the hood sides. See Fig. 24 and 25. Secure hood divider with 2 screws on each hood side. The hood divider is also used as the bot- tom filter rack for the aluminum filter.
7.Open the filter clips which are located underneath the hood top. Insert the aluminum filter into the bottom filter rack (hood divider). Push the filter into position past the open filter clips. Close the filter clips to lock the filter into place. See Fig. 25.
8.Caulk the ends of the joint between the unit top panel and the hood top. See Fig. 23.
9.Replace the filter access panel.
10.Install all EconoMi$er IV accessories. EconoMi$er IV wiring is shown in Fig. 26. EconoMi$er2 wiring is shown in Fig. 27.
Barometric flow capacity is shown in Fig. 28. Outdoor air leakage is shown in Fig. 29. Return air pressure drop is shown in Fig. 30.
22 1/4”
LEFT
HOOD
SIDE
24 9/16”
B
TOP
PANEL
INDOOR COIL
ACCESS PANEL
SCREW
40 3/8”
HOOD DIVIDER
DIVIDER
OUTSIDE
AIR
HOOD
CLEANABLE
ALUMINUM FILTER FILTER
Fig. 24 — Outdoor-Air Hood Construction
BAROMETRIC RELIEF
FILTER CLIP
Fig. 25 — Filter Installation
FOR OCCUPANCY CONTROL
REPLACE JUMPER WITH
LEGEND | Potentiometer Defaults Settings: | ||
DCV— Demand Controlled Ventilation | Power Exhaust | Middle | |
Minimum Pos. | Fully Closed | ||
IAQ — Indoor Air Quality | |||
DCV Max. | Middle | ||
LA — Low Ambient Lockout Device | |||
DCV Set | Middle | ||
OAT — | |||
Enthalpy | C Setting | ||
POT — Potentiometer | |||
|
|
RAT —
NOTES:
1.620 ohm, 1 watt 5% resistor should be removed only when using differential enthalpy or dry bulb.
2.If a separate
3.For
Fig. 26 — EconoMi$er IV Wiring
19