To align the fan and motor pulleys: 1. Loosen the fan pulley setscrews.

2. Slide the fan pulley along the fan shaft.

3. Make angular alignment by loosening the motor from the mounting plate.

To adjust belt tension:

1. Loosen the fan motor mounting nuts.

2. Sizes 008 and 009 — Slide the motor mounting plate away from the fan scroll for proper belt tension (1/2-in. deflection with 5 to 10 lb of force) and tighten the mount- ing nuts (see Fig. 38).

Size 012 — Slide the motor mounting plate downward to tighten belt tension (1/2-in. deflection with 5 to 10 lb of force). Secure the motor mounting plate nuts. See Fig. 39.

3. Adjust the bolt and nut on the mounting plate to secure the motor in fixed position.

MOTOR MOUNTING

PLATE NUTS

Fig. 39 — Typical Belt-Drive Motor Mounting for

Size 012

Fig. 38 — Typical Belt-Drive Motor Mounting for

Fig. 40 — Indoor-Fan Pulley Adjustment

 

Size 008 and 009

 

 

 

 

 

 

 

 

 

 

 

 

Table 9 — Fan Motor Performance

 

 

 

 

 

 

 

 

 

 

UNIT

INDOOR-FAN

 

UNIT

MAXIMUM ACCEPTABLE

 

MAXIMUM ACCEPTABLE

MAXIMUM

50TFQ

MOTOR

 

VOLTAGE

 

CONTINUOUS BHP*

 

OPERATING WATTS

AMP DRAW

 

Standard,

 

208/230

 

 

 

 

6.0

 

 

460

 

2.40

 

2120

3.0

 

Alternate

 

 

 

008

 

575

 

 

 

 

3.0

 

 

 

 

 

 

 

 

208/230

 

 

 

 

11.7

 

 

 

 

 

 

 

 

High Static

 

460

 

3.70

 

3313

5.5

 

 

 

575

 

 

 

 

5.5

 

 

 

208/230

 

 

 

 

6.0

 

Standard

 

460

 

2.40

 

2120

3.0

009

 

 

575

 

 

 

 

3.0

 

 

208/230

 

 

 

 

11.7

 

 

 

 

 

 

 

 

High Static

 

460

 

3.70

 

3313

5.5

 

 

 

575

 

 

 

 

5.5

 

 

 

208/230

 

 

 

 

6.0

 

Standard

 

460

 

2.40

 

2120

3.0

 

 

 

575

 

 

 

 

3.0

 

 

 

208/230

 

 

 

 

8.6

012

Alternate

 

460

 

2.90

 

2615

3.9

 

 

 

575

 

 

 

 

3.9

 

 

 

208/230

 

 

 

 

17.3

 

High Static

 

460

 

5.25

 

4400

8.5

 

 

 

575

 

 

 

 

8.5

LEGEND

BHP — Brake Horsepower

*Extensive motor and electrical testing on these units ensures that the full horsepower range of the motors can be utilized with confidence. Using fan motors up to the horsepower ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.