Carrier 50TFQ008-012 specifications Airflow, Refer to page 43 General Fan Performance Notes

Models: 50TFQ008-012

1 56
Download 56 pages 18.09 Kb
Page 31
Image 31

Table 15 — Fan Performance, 50TFQ009 — Vertical Discharge Units; Standard Motor and Drive*

AIRFLOW

 

 

 

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

0.2

 

 

 

 

0.4

 

 

 

 

 

0.6

 

 

 

 

0.8

 

 

1.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

2550

557

0.79

733

 

631

 

0.98

 

910

 

697

 

1.17

 

1095

756

 

1.38

1287

811

1.60

1488

2600

565

0.83

770

 

638

 

1.02

 

950

 

703

 

1.22

 

1138

762

 

1.43

1333

816

1.65

1536

2700

581

0.91

848

 

652

 

1.11

 

1034

 

716

 

1.32

 

1228

774

 

1.53

1428

828

1.75

1636

2800

597

1.00

932

 

667

 

1.21

 

1124

 

729

 

1.42

 

1323

786

 

1.64

1529

839

1.87

1742

2900

613

1.09

1020

 

681

 

1.31

 

1220

 

743

 

1.53

 

1425

799

 

1.75

1636

851

1.99

1855

3000

629

1.20

1115

 

696

 

1.42

 

1321

 

756

 

1.64

 

1532

812

 

1.88

1749

863

2.12

1973

3100

646

1.30

1217

 

711

 

1.53

 

1428

 

770

 

1.76

 

1645

825

 

2.00

1869

875

2.25

2098

3200

662

1.42

1324

 

726

 

1.65

 

1542

 

784

 

1.89

 

1765

838

 

2.14

1994

888

2.39

2229

3300

679

1.54

1438

 

741

 

1.78

 

1663

 

798

 

2.03

 

1892

851

 

2.28

2126

3400

695

1.67

1558

 

756

 

1.92

 

1790

 

812

 

2.17

 

2025

3500

712

1.81

1686

 

772

 

2.06

 

1923

 

827

 

2.32

 

2165

3600

729

1.95

1820

 

787

 

2.21

 

2065

 

3700

746

2.10

1962

 

803

 

2.37

 

2213

 

3750

754

2.18

2036

 

3800

763

2.26

2112

 

3900

 

4000

 

4100

 

4200

 

4250

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

1.2

 

 

 

 

1.4

 

 

 

 

 

1.6

 

 

 

 

1.8

 

 

2.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

Watts

 

Rpm

 

Bhp

 

Watts

 

Rpm

 

Bhp

 

Watts

Rpm

 

Bhp

Watts

Rpm

Bhp

Watts

2550

862

 

1.82

1697

 

910

 

2.05

 

1913

 

955

 

2.29

 

2138

 

2600

867

 

1.87

1747

 

915

 

2.11

 

1966

 

960

 

2.35

 

2193

 

2700

878

 

1.99

1852

 

925

 

2.23

 

2076

 

 

 

 

2800

889

 

2.11

1963

 

936

 

2.35

 

2192

 

 

 

 

2900

900

 

2.23

2080

 

 

 

 

 

 

 

3000

912

 

2.36

2204

 

 

 

 

 

 

 

3100

 

 

 

 

 

 

 

 

3200

 

 

 

 

 

 

 

 

3300

 

 

 

 

 

 

 

 

3400

 

 

 

 

 

 

 

 

3500

 

 

 

 

 

 

 

 

3600

 

 

 

 

 

 

 

 

3700

 

 

 

 

 

 

 

 

3750

 

 

 

 

 

 

 

 

3800

 

 

 

 

 

 

 

 

3900

 

 

 

 

 

 

 

 

4000

 

 

 

 

 

 

 

 

4100

 

 

 

 

 

 

 

 

4200

 

 

 

 

 

 

 

 

4250

 

 

 

 

 

 

 

 

LEGEND

Bhp — Brake Horsepower Input to Fan

Watts — Input Watts to Motor

*Motor drive range: 685 to 935 rpm. All other rpms require field- supplied drive.

Refer to page 43 General Fan Performance Notes.

NOTES:

1.Boldface indicates field-supplied drive is required.

2.Maximum continuous bhp is 2.40.

31