Table 5 — PremierLink™ Sensor Usage

Table 5 — PremierLink™ Sensor Usage

APPLICATION

OUTDOOR AIR

RETURN AIR

OUTDOOR AIR

RETURN AIR

TEMPERATURE SENSOR

TEMPERATURE SENSOR

ENTHALPY SENSOR

ENTHALPY SENSOR

 

Dry Bulb

 

 

 

 

Temperature with

 

 

 

 

PremierLink™*

Included —

(PremierLink

HH79NZ017

 

 

 

requires 4-20 mA

 

 

 

 

Actuator)

 

 

 

 

Differential Dry Bulb

 

 

 

 

Temperature with

 

Required —

 

 

PremierLink*

Included —

 

 

33ZCT55SPT

(PremierLink

HH79NZ017

or Equivalent

 

 

requires 4-20 mA

 

 

 

 

 

 

 

Actuator)

 

 

 

 

Single Enthalpy with

 

 

 

 

PremierLink*

Included —

 

Required —

 

(PremierLink

Not Used

HH57AC077

requires 4-20 mA

 

 

 

 

 

 

Actuator)

 

 

 

 

Differential Enthalpy

 

 

 

 

with PremierLink*

Included —

 

Required —

Required —

(PremierLink

Not Used

HH57AC077

HH57AC078

requires 4-20 mA

 

 

 

 

 

Actuator)

 

 

 

 

*PremierLink control requires Supply Air Temperature sensor 33ZCSENSAT and

Outdoor Air Temperature Sensor HH79NZ017 — Included with factory-installed PremierLink control; field-supplied and field-installed with field-installed PremierLink control.

NOTES:

1.CO2 Sensors (Optional):

33ZCSENCO2 — Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor.

33ZCASPCO2 — Aspirator box used for duct-mounted CO2 room sensor.

33ZCT55CO2 — Space temperature and CO2 room sensor with override.

33ZCT56CO2 — Space temperature and CO2 room sensor with override and set point.

2.All units include the following Standard Sensors:

Outdoor-Air Sensor — 50HJ540569 — Opens at 67 F, closes at 52 F, not adjustable.

Mixed-Air Sensor — HH97AZ001 — (PremierLink control requires Supply Air Temperature sensor 33ZCSENSAT and Outdoor Air Temperature Sensor HH79NZ017)

Compressor Lockout Sensor — 50HJ540570 — Opens at 35 F, closes at 50 F.

Fig. 15A — PremierLink Controller

15

Page 15
Image 15