Carrier 50TFQ008-012 specifications Fan Rpm at Motor Pulley Settings

Models: 50TFQ008-012

1 56
Download 56 pages 18.09 Kb
Page 27
Image 27

Table 10 — Fan Rpm at Motor Pulley Settings*

UNIT

 

 

 

 

 

MOTOR PULLEY TURNS OPEN

 

 

 

 

 

50TFQ

 

0

1/2

1

11/2

2

 

21/2

3

31/2

 

4

41/2

5

51/2

6

008†

840

815

790

765

740

 

715

690

665

 

635

615

590

008**

 

935

910

885

860

835

 

810

785

760

 

735

710

685

008††

1080

1025

1007

988

970

 

952

933

915

 

897

878

860

009†

935

910

885

860

835

 

810

785

760

 

735

710

685

009††

1080

1025

1007

988

970

 

952

933

915

 

897

878

860

012†

935

910

885

860

835

 

810

785

760

 

735

710

685

012**

 

1085

1060

1035

1010

985

 

960

935

910

 

885

860

835

012††

1130

1112

1087

1062

1037

 

1012

987

962

 

937

912

887

862

830

*Approximate fan rpm shown.

†Indicates standard motor and drive package.

**Indicates alternate drive package only. ††Indicates high-static motor and drive package.

Table 11A — Electric Heater Static Pressure* (in. wg) — 50TFQ008-012

COMPONENT

 

 

 

 

 

CFM

 

 

 

 

2250

2500

3000

3500

4000

 

4500

5000

5500

6000

6250

 

 

1 Heater Module

0.02

0.03

0.05

0.07

0.08

 

0.10

0.12

0.14

0.16

0.17

2 Heater Modules

0.03

0.05

0.07

0.09

0.12

 

0.14

0.16

0.19

0.21

0.20

*The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be used in conjunction with the Fan Performance tables to deter- mine blower rpm and watts.

Table 11B — EconoMi$er IV and EconoMi$er2 Static Pressure* (in. wg) — 50TFQ008-012

COMPONENT

 

 

 

 

 

 

CFM

 

 

 

 

 

 

2250

2500

2750

3000

3250

3500

3750

4000

4250

4500

4750

5000

5250

6250

 

Vertical EconoMi$er IV and EconoMi$er2

0.06

0.075

0.09

0.115

0.13

0.15

0.17

0.195

0.22

0.25

0.285

0.325

0.36

Horizontal EconoMi$er IV and EconoMi$er2

0.1

0.125

0.15

0.18

0.21

0.25

0.275

0.3

0.34

0.388

*The static pressure must be added to external static pressure. The sum and the outdoor entering-air cfm should then be used in conjunction with the Fan Performance tables to determine blower rpm and watts.

27