58CT
7 |
See notes 1, 2, 3, 4, 12, 13, 14, 15, and 17 on the page following these figures
A03182
Fig. 30 - Dual Fuel Thermostat with Two-Stage Furnace
and Two-Speed Heat Pump
See notes 2, 11, and 12 on the page following these figures
A03183
Fig. 31 - Two-Stage Thermostat with Two-Stage Furnace
and Two-Speed Air Conditioner
See notes 1 and 2 on the page following these figures
A03184
Fig. 32 - Single-Stage Thermostat with Two-Stage Furnace and Two-Speed Air Conditioner
NOTES: For Figures
1.Heat pump MUST have a high pressure switch for dual fuel applications.
2.Refer to outdoor equipment Installation Instructions for additional information and setup procedure.
3.Outdoor Air Temperature Sensor must be attached in all dual fuel applications.
4.Dip switch No. 1 on Thermidistat should be set in OFF position for air conditioner installations. This is factory default.
5.Dip switch No. 1 on Thermidistat should be set in ON position for heat pump installations.
6.Dip switch No. 2 on Thermidistat should be set in OFF position for
7.Dip switch No. 2 on Thermidistat should be set in ON position for
8.Configuration Option No. 10 “Dual Fuel Selection” must be turned ON in all dual fuel applications.
9.NO connection should be made to the furnace HUM terminal when using a Thermidistat.
10.Optional connection: If wire is connected, dip switch
11.Optional connection: If wire is connected, ACRDJ jumper on furnace control should be removed to allow Thermidistat/Thermostat to control outdoor unit staging.
12.When using both a
13.The RVS Sensing terminal “L” should not be connected. This is internally used to sense defrost operation.
14.DO NOT SELECT the “FURNACE INTERFACE” or “BALANCE POINT” option on the
15.Dip switch D on Dual Fuel Thermostat should be set in OFF position for
16.Dip switch D on Dual Fuel Thermostat should be set in ON position for
24