58CT

7

See notes 1, 2, 3, 4, 12, 13, 14, 15, and 17 on the page following these figures

A03182

Fig. 30 - Dual Fuel Thermostat with Two-Stage Furnace

and Two-Speed Heat Pump

See notes 2, 11, and 12 on the page following these figures

A03183

Fig. 31 - Two-Stage Thermostat with Two-Stage Furnace

and Two-Speed Air Conditioner

See notes 1 and 2 on the page following these figures

A03184

Fig. 32 - Single-Stage Thermostat with Two-Stage Furnace and Two-Speed Air Conditioner

NOTES: For Figures 26---32

1.Heat pump MUST have a high pressure switch for dual fuel applications.

2.Refer to outdoor equipment Installation Instructions for additional information and setup procedure.

3.Outdoor Air Temperature Sensor must be attached in all dual fuel applications.

4.Dip switch No. 1 on Thermidistat should be set in OFF position for air conditioner installations. This is factory default.

5.Dip switch No. 1 on Thermidistat should be set in ON position for heat pump installations.

6.Dip switch No. 2 on Thermidistat should be set in OFF position for single---speed compressor operation. This is factory default.

7.Dip switch No. 2 on Thermidistat should be set in ON position for two---speed compressor operation.

8.Configuration Option No. 10 “Dual Fuel Selection” must be turned ON in all dual fuel applications.

9.NO connection should be made to the furnace HUM terminal when using a Thermidistat.

10.Optional connection: If wire is connected, dip switch SW1---2 on furnace control should be set in ON position to allow Thermidistat/Thermostat to control furnace staging.

11.Optional connection: If wire is connected, ACRDJ jumper on furnace control should be removed to allow Thermidistat/Thermostat to control outdoor unit staging.

12.When using both a two---stage furnace and a two---stage heat pump, the furnace must control its own high ---stage heating operation via furnace control algorithm.

13.The RVS Sensing terminal “L” should not be connected. This is internally used to sense defrost operation.

14.DO NOT SELECT the “FURNACE INTERFACE” or “BALANCE POINT” option on the two---speed heat pump control board. This is controlled internally by the Thermidistat/Dual Fuel Thermostat.

15.Dip switch D on Dual Fuel Thermostat should be set in OFF position for single---speed compressor operation. This is factory default.

16.Dip switch D on Dual Fuel Thermostat should be set in ON position for two---speed compressor operation.

24

Page 24
Image 24
Carrier 58CTA/CTX instruction manual See notes 2, 11, and 12 on the page following these figures