Information About Configuring PROFINET
PROFINET devices are integrated by using a general station description (GSD) file that cont ains the data
for engineering and data exchange between the I/O controller, the I/O supervisor, and the I/O devices,
including the switch. Each PROFINET I/O field device must have an associated GSD file that describes
the properties of the device and contains all this information required for configuration:
Device identification information (device ID, vendor ID and name, product family, number of ports)
Number and types of pluggable modules
The Cisco IE 2000 8-port expander modules are not hot-swappable. Turn off the switch before
connecting or disconnecting expander modules.
Error text for diagnostic information
Communication parameters for I/O devices, including the minimum cycle time, the r eduction ratio,
and the watch dog time
Tab l e 9-1 PROFINET I/O Switch Attributes
PROFINET I/O Switch Configuration
Attributes Value or Action
Device name Configures a name for the device.
TCP/IP IP address, subnet mask, default gateway, SVI.
Primary temperature alarm Enables or disables monitoring for the specified alarm.
Secondary temperature alarm Enables or disables monitoring for the specified alarm.
RPS failed alarm Enables or disables monitoring for the specified alarm.
Relay major alarm Enables or disables monitoring for the specified alarm.
Reset to factory defaults Uses the PROFINET I/O controller to reset the switch to factory defaults.
This action removes the startup configuration and reloads the switch.
Relay major configuration Specifies the type of port alarm (for example, link fault) that triggers the
major relay. Any port configured with the specified alarm type can
trigger the major relay.
Tab l e 9-2 PROFINET I/O Port Attributes
PROFINET I/O Port Configuration Attributes Value or Action
Speed 10/100/1000/auto,
Duplex Half/full/auto,
Port mode Access/trunk,
Link status Shut down/no shut down,
Configure rate limiting Broadcast, unicast, multicast threshold exceeds configured levels.
Port link fault alarm Enables or disables monitoring for specified alarm.
Port not forwarding alarm Enables or disables monitoring for specified alarm.
Port not operating alarm Enables or disables monitoring for specified alarm.