Cooper Bussmann CT02MAN manual Grounding. a Metallic Cable Trays

Models: CT02MAN

1 60
Download 60 pages 43.63 Kb
Page 28
Image 28

UL Listed Conduit To

 

Cable Tray Clamp

2 Inch Rigid Metal Conduit

Conduit Bushing

 

 

 

 

 

 

 

 

Position Of The First

 

 

 

 

 

 

 

 

Conduit Support

 

Cable Tray

 

 

 

 

 

 

 

 

 

 

 

 

 

From The Cable Tray

 

Side Rail

 

 

 

 

 

 

 

 

 

 

 

 

 

(Conduit Must Be

 

 

 

 

 

16 Feet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Securely Fastened To

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The Support)

 

 

 

 

See NEC® Table 344.30(B)(2) To Obtain The

 

Cable Tray

 

Support Requirements For Other Conduit Sizes.

 

 

 

 

 

 

 

 

 

 

 

 

 

Conduit Terminated On And Supported By The Cable Tray Side Rail.

Installation For Qualifying Industrial Facilities As Per 392.6(J).

UL Listed Conduit To

 

Cable Tray Clamp

Any Size Of Rigid Metal Conduit

Conduit Bushing

 

 

 

 

 

 

 

 

Position Of The First

 

 

 

 

 

 

 

 

Conduit Support

 

 

 

 

 

 

From The Cable Tray

 

Cable Tray

 

 

 

Side Rail

 

 

 

 

(Conduit Must Be

 

 

 

 

 

3 Feet or 5 Feet

 

 

Securely Fastened To

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The Support)

 

 

 

 

 

 

 

 

 

 

 

 

See Section 344.30

 

 

 

 

 

 

 

 

 

 

 

 

Cable Tray

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Conduit Terminated On The Cable Tray Side Rail.

Installation For Commercial And Non-Qualifying Industrial Facilities As Per 392.6(J).

392.7.Grounding. (A) Metallic Cable

Trays.

All metallic cable trays shall be grounded as required in Article 250 regardless of whether or not the cable tray is being used as an equipment grounding conductor (EGC).

The EGC is the most important conductor in an electrical system as its function is electrical safety.

There are three wiring options for providing an EGC in a cable tray wiring system: (1) An EGC conductor in or on the cable tray. (2) Each multiconductor cable with its individual EGC conductor. (3) The cable tray itself is used as the EGC in qualifying facilities.