TABLE I

TEMPERATURE RISE TESTS, CABLE TRAY CONNECTORS,

CLASS II ALUMINUM LADDER CABLE TRAY

Test

 

 

 

 

 

Connector Data

 

 

 

Current

Test

I2T

 

C1

 

 

C2

 

 

C3

 

Amps

Time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

And

Cycles

mult.

Type

No. &

Temp.

Type

No. &

Temp.

Type

No. &

Temp.

Fuse

 

by

Of

Type

Rise

Of

Type

Rise

Of

Type

Rise

Size*

 

106

Connector

Bolts

°C

Connector

Bolts

°C

Connector

Bolts

°C

 

 

 

 

 

 

 

 

 

 

 

 

7,900

 

 

Adj. Vert.

 

 

3/0 CU

AL-CU

 

Rigid

 

 

1,200A

66

69

1 Bolt**

4

6

Bond

Lugs

18

Clean

2

8

Fuse

 

 

 

Steel

 

 

 

 

 

Steel

 

7,900

 

 

Rigid

 

 

3/0 CU

AL-CU

 

Rigid

 

 

1,200A

82

85

Corroded

4

10

Bond

Lugs

22

Clean

2

9

Fuse

 

 

 

Steel

 

 

 

 

 

Steel

 

 

 

 

 

 

 

 

 

 

 

 

 

12,000

120

288

Rigid

2

50

3/0 CU

AL-CU

104

Rigid

2

32

 

 

 

Corroded

Nylon

 

Bond

Lugs

 

Clean

Steel

 

 

 

 

 

 

 

 

 

 

 

 

 

12,000

124

297

Rigid

4

40

Rigid

4

46

Rigid

4

21

 

 

 

Corroded

Steel

 

Corroded

Lugs

 

Clean

Steel

 

 

 

 

 

 

 

 

 

 

 

 

 

34,600

14

280

Rigid

2

34

3/0 CU

AL-CU

75

Rigid

2

29

 

 

 

Corroded

Nylon

 

Bond

Lugs

 

Clean

Steel

 

 

 

 

 

 

 

 

 

 

 

 

 

34,400

14

276

Rigid

4

28

Rigid

4

35

Rigid

4

20

 

 

 

Corroded

Nylon

 

Corroded

Steel

 

Clean

Steel

 

 

 

 

 

 

 

 

 

 

 

 

 

TABLE II

TEMPERATURE RISE TESTS, CABLE TRAY CONNECTORS,

CLASS II STEEL LADDER CABLE TRAY

Test

 

 

 

 

 

Connector Data

 

 

 

Current

Test

I2T

 

C1

 

 

C2

 

 

C3

 

 

 

 

 

 

 

Amps

Time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

And

Cycles

mult.

Type

No. &

Temp.

Type

No. &

Temp.

Type

No. &

Temp.

Fuse

 

by

Of

Type

Rise

Of

Type

Rise

Of

Type

Rise

Size*

 

106

Connector

Bolts

°C

Connector

Bolts

°C

Connector

Bolts

°C

 

 

 

 

 

 

 

 

 

 

 

 

1,980

52

3.4

Adj. Vert.

4

2

No. 6 CU

AL-CU

10

Rigid

2

3

200A, FU

 

 

1 Bolt**

 

 

Bond

Lugs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1,970

394

25.5

Adj. Vert.

4

9

No. 6 CU

AL-CU

***

Rigid

2

15

400A, FU

 

 

1 Bolt**

 

 

Bond

Lugs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1,960

8100

51.8

Adj. Vert.

4

18

Rigid

4

23

Rigid

2

32

400A, FU

 

 

1 Bolt**

 

 

 

 

 

 

 

 

12,000

120

288

Adj. Vert.

4

94

Adj. Vert.

4

89

Rigid

4

81

 

 

 

2 Bolts**

 

 

2 Bolts**

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12,000

123

295

Rigid

4

70

Rigid

4

87

Rigid

4

85

 

 

 

 

 

 

 

 

 

 

 

 

34,000

13

250

Rigid

4

71

Rigid

4

57

Rigid

4

69

 

 

 

 

 

 

 

 

 

 

 

 

*Test current was interrupted in a predetermined time when a fuse was not used.

**1 or 2 Bolts - Number of bolts installed on the adjustable vertical connector hinge.

***The No. 6 bonding jumper melted and opened the circuit when protected by 400A fuse.

 

(See Page 29 - Figure 1 for Temperature Rise Test illustration)

 