Table 250.122. Minimum Size Equipment Grounding

Conductors for Grounding Raceways and Equipment

Rating or Setting of

 

Size

Automatic Overcurrent

(AWG or kcmil)

Device in Circuit Ahead

 

 

of Equipment, Conduit,

 

Aluminum or

etc., Not Exceeding

 

Copper-Clad

(Amperes)

Copper

Aluminum*

15

14

12

20

12

10

30

10

8

40

10

8

60

10

8

100

8

6

200

6

4

300

4

2

400

3

1

500

2

1/0

600

1

2/0

800

1/0

3/0

1000

2/0

4/0

1200

3/0

250

1600

4/0

350

2000

250

400

2500

350

600

3000

400

600

4000

500

800

5000

700

1200

6000

800

1200

Reprinted with permission from NFPA 70-1999, the National Electrical Code®, Copyright© 1998, National Fire