Discontinuous Joints

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Require Bonding

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bonding Jumper Not

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Required For Rigidly

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For Qualifying Facilities

 

 

 

 

 

 

 

 

 

 

 

Bolted Joints

 

 

 

 

 

 

 

 

 

 

 

Bond

 

 

 

EGCs in the Cables or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EGC Cables Are Not

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Required If Rating Of The

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Feeder Overcurrent Device

 

 

 

 

 

 

 

 

 

 

 

Conduit

 

Permits Using The Tray

 

 

 

 

 

 

 

 

 

 

 

 

 

For the EGC

 

 

 

 

 

 

 

 

 

 

 

Three Phase

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor Installation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor Control Center

 

 

 

 

 

 

 

 

 

Bond

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EGC In

 

 

 

 

 

 

 

 

Switchgear

 

 

 

 

 

 

 

 

 

 

 

 

 

Cable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Transformer

 

 

 

 

 

EGC

 

 

 

 

 

 

(Solidly

 

 

 

 

 

 

 

 

 

Building Steel

 

 

Grounded

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Secondary)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ground Bus

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bonded To

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enclosure

 

 

Lightning

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Grounding

 

 

 

 

 

 

 

 

 

 

 

System Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Correct Bonding Practices To Assure That The

Cable Tray System Is Properly Grounded

If an EGC cable is installed in or on a cable tray, it should be bonded to each or alternate cable tray sections via grounding clamps (this is not required by the NEC® but it is a desirable practice). In addition to providing an electrical connection between the cable tray sections and the EGC, the grounding clamp mechanically anchors the EGC to the cable tray so that under fault current conditions the magnetic forces do not throw the EGC out of the cable tray.

A bare copper equipment grounding conductor should not be placed in an aluminum cable tray due to the potential for electrolytic corrosion of the aluminum cable tray in a moist environment. For such installations, it is best to use an insulated conductor and to remove the insulation where bonding connections are made to the cable tray, raceways, equipment enclosures, etc. with tin or zinc plated connectors.

See Table 250.122 on page 51 for the minimum size EGC for grounding raceway and equipment.

Cable Tray Manual