Cornelius QUANTUM SERIES No cooling con’t No water dispensed, concentrate only, 720901120

Models: QUANTUM SERIES

1 37
Download 37 pages 15.63 Kb
Page 14
Image 14
No cooling (con’t)

Quantum Series Installation and Service Manual

No cooling (con’t)

No water dispensed, concentrate only.

Defective start relay located on upper rear shelf inside dispenser

Compressor starts but hums and trips overload

Compressor starts but does not switch off of start winding

Compressor short cycles on overload

Refrigerant leak

No water to dispenser

Water supply line inside refrigerated cabinet dis- connected from pump platform

Water solenoid located on pump platform clogged or defective

Main water solenoid/ strainer located at base of dispenser is clogged, binding or defective

Water supply pressure is greater than 80 psi (5.5 bar)

There should be line voltage on the black wire of the relay when there is line voltage present on the orange OR yellow wire. Replace relay if it fails this test.

Seized or shorted compressor, replace.

Relay or compressor is defective. Test and replace faulty item.

Excessively high discharge pres-

sure due to restricted con- denser or inoperative condenser fan motor

Repair leak. Evacuate and recharge system.

Restore water

Reconnect

Disassemble and clean solenoid. Replace if necessary.

Remove and clean strainer. Con- firm 28VDC is present at sole- noid during dispense. Confirm solenoid coil is not open. Disas- semble and clean solenoid.

Add external regulator and lower pressure to 50 psi (3.5 bar)

720901120

- 12 -

Page 14
Image 14
Cornelius QUANTUM SERIES No cooling con’t No water dispensed, concentrate only, No water to dispenser, 720901120