Cornelius QUANTUM SERIES Concentrate refill light does not come on at all con’t Warm Drink

Models: QUANTUM SERIES

1 37
Download 37 pages 15.63 Kb
Page 17
Image 17
Concentrate refill light does not come on at all (con’t)

Quantum Series Installation and Service Manual

Concentrate refill light does not come on at all (con’t)

Warm Drink

Water continuously drips from nozzle when in OFF mode

No Flush Cycle

Concentrate warm, water cold

Improperly loaded tube

Bad VRB board

Bad portion control

Incoming water supply too warm

Ambient air too warm

Excessive demand on dis- penser

Dirty condenser coil

Inoperative condenser fan

Defective water thermostat

Loss of refrigerant charge due to leak in system

Main water solenoid at base of unit or water solenoid on pump platform not shutting off tightly

Run/Flush switch on pump platform in Run mode

Defective Run/Flush switch on pump platform (con- centrate continues to dispense while in Flush mode)

Concentrate thermostat is turned off or not cali- brated properly

Concentrate thermostat defective (stuck open)

Defective start relay located on upper rear shelf inside dispenser

Refer to concentrate loading sec- tion of this manual

Replace VRB board

Replace portion control

Optimum performance is achieved

when the dispenser utilizes water from a pre-cooler

Relocate dispenser

Add water pre-cooler or second dispenser

Clean condenser coil

Replace condenser fan motor

Replace thermostat

Repair leak and recharge system

Clean solenoid(s), replace parts as necessary

Move switch to Flush position

Replace Run/Flush switch

Calibrate to be 34oF -40 oF (1.1 oC

–4.5 oC)

Replace thermostat and calibrate to 34oF -40 oF (1.1 oC –4.5 oC)

There should be line voltage on the black wire of the relay when there is line voltage present on the orange OR yellow wire. Replace relay if it fails this test.