19-PIN CONNECTOR ELECTRICAL CONNECTIONS 
 69
5
5.5  ID-NET™ INTERFACE Pin Name  Function 
R ID+  ID-NET™ network + 
P ID-  ID-NET™ network - 
L GND  Ground 
The following instructions are referred to Figure 83, Figure 84 and Figure 85. 
 The general cable type specifications are: CAT5 twisted pair + additional CAT5 twisted 
pair, shielded cable AWG 24 (or AWG 22) stranded flexible. 
We recommend using DeviceNet cables (drop or trunk type) to the following reference 
standards: 
AN50325 – IEC 62026 
UL STYLE 2502 80°C 30V 
 Cable Shield MUST be connected to earth ground ONLY at the Master. 
 NEVER use ID-NET™ cable shield as common reference. 
 The ID-NET™ max cable length depends on the baudrate used, (see the Baudrate Table 
below). 
 For Common Power Connections use only 2 wires (R and P). 
-  DC Voltage Power cable (Vdc – GND) should be handled as a signal cable (i.e. do 
not put it together with AC cable): 
-  Wire dimensioning must be checked in order to avoid voltage drops greater than 0.8 
Volts. 
-  Cable should lie down as near as possible to the ID-NET™ cable (avoiding wide 
loops between them). 
 Reader's chassis may be connected to earth. 
 Network inside the same building. 
Baudrate Table 
Baud Rate  125 kbps  250 kbps  500 kbps  1Mbps 
Cable Length  1200 m  900 m  700 m  * 
* Application dependent, contact your Datalogic Automation representative for details. 
NOTE 
The default ID-NET™ baudrate is 500 kbps. Lower ID-NET™ baudrates 
allow longer cable lengths. The baudrate is software configurable by 
authorized Datalogic Automation personnel only.