Desa LHP) (V)L36(EP, LZPR) 5.3or applicable local codes, Continued, Ventilation Air

Models: LEN) (V)L32(HP LHN) (V)L36(EN LHP) (V)L36(EP L32, L36 L36, L42, L32, L36, L36, L42 L32, L36, L32, L36, VL36, L42, L36, L42 LZPR) LEP) (V)L36(ZNR

1 44
Download 44 pages 7.35 Kb
Page 8
Image 8
Example:

AIR FOR COMBUSTION

AND VENTILATION

Continued

1.Determine the volume of the space (length x width x height).

Length x Width x Height =________ cu. ft. (volume of space)

Example: Space size 22 ft. (length) x 18 ft. (width) x 8 ft. (ceiling height) = 3168 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

_______(volume of space) x 20 = (Maximum Btu/Hr the space can support)

Example: 3168 cu. ft. (volume of space) x 20 = 63,360 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

__________ Btu/Hr

Gas water heater*

__________ Btu/Hr

Gas furnace

__________ Btu/Hr

Vented gas heater

__________

Btu/Hr

Gas fireplace logs

__________

Btu/Hr

Other gas appliances* +

________

Btu/Hr

Total

=

________

Btu/Hr

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

Example:

40,000

 

Gas water heater

 

__________ Btu/Hr

Vent-free heater

39,000

Btu/Hr

+ ________

Total

79,000

Btu/Hr

= ________

4. Compare the maximum Btu/Hr the space can

support with the actual amount of Btu/Hr used.

__________ Btu/Hr (maximum the space

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building.

B.Vent room directly to the outdoors. See Ven- tilation Air From Outdoors, page 9.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an un- confined space. You will need no additional fresh air ventilation.

5.3or applicable local codes. WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilationairbyoneofthemethods described in the National Fuel Gas Code,ANSIZ223.1/NFPA54Section

5.3or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining un- confined space. When ventilating to an adjoining unconfined space, you must provide two perma- nent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 4). You can also remove door into adjoining room (see option 3, Figure 3). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

can support)

__________ Btu/Hr (actual amount of

Btu/Hr used)

Example: 63,360 Btu/Hr (maximum

the space can support)

79,000 Btu/Hr (actual amount of Btu/Hr used)

Ventilation

 

Grills

 

Into

Or

Adjoining

Remove

Room,

Door into

Option 1

Adjoining

 

 

Room,

 

Option

 

3

12"

Ventilation Grills

Into Adjoining Room,

Option 2

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

12"

Figure 3 - Ventilation Air from Inside

Building

8

www.desatech.com

115254-01A

Page 8
Image 8
Desa LHP) (V)L36(EP, LZPR) 5.3or applicable local codes, Continued, Ventilation Air from Inside Building