Desa LEN) (V)L32(HP, LZPR), LHP) (V)L36(EP Continued, ODS/pilot lights but flame goes

Models: LEN) (V)L32(HP LHN) (V)L36(EN LHP) (V)L36(EP L32, L36 L36, L42, L32, L36, L36, L42 L32, L36, L32, L36, VL36, L42, L36, L42 LZPR) LEP) (V)L36(ZNR

1 44
Download 44 pages 7.35 Kb
Page 30
Image 30
ODS/pilot lights but flame goes

TROUBLESHOOTING

Continued

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

ODS/pilot lights but flame goes

1. Control knob not fully

1.

Press in control knob fully

out when control knob is re-

 

pressed in

2.

After ODS/pilot lights, keep

leased

2. Control knob not pressed in

 

 

long enough

 

control knob pressed in 30

 

3.

Safety interlock system has

 

seconds

 

3.

Wait one minute for safety in-

 

 

been triggered

 

terlock system to reset. Repeat

 

4.

Equipment shutoff valve not

 

ignition operation

 

4.

Fully open equipment shutoff

 

 

fully open

 

valve

 

5.

Pilot flame not touching

5.

A) Contact local natural or

 

 

thermocouple, which allows

 

propane/LP gas company

 

 

thermocouple to cool, caus-

 

 

 

 

ing pilot flame to go out. This

 

B) Clean ODS/pilot (see

 

 

problem could be caused by

 

Cleaning and Maintenance,

 

 

one or both of the following:

 

page 28) or replace ODS/pilot

 

 

A) Low gas pressure

 

assembly

 

 

B) Dirty or partially clogged

 

 

 

 

ODS/pilot

 

 

 

6.

Thermocouple connection

6.

Hand tighten until snug, then

 

 

loose at control valve

 

tighten 1/4 turn more

 

7.

Thermocouple damaged

7.

Replace pilot assembly

 

8.

Control valve damaged

8.

Replace control valve

 

 

 

 

One or both burners do not light

1. Inlet gas pressure is too low

1.

Contact local natural or pro-

after ODS/pilot is lit

2.

Burner orifice(s) clogged

 

pane/LP gas company

 

2.

Clean burner(s) (see Cleaning

 

 

 

 

and Maintenance, page 28) or

 

3.

Mislocated crossover tube

 

replace burner orifice(s)

 

3.

Contact qualified service person

 

4.

Remoteselector in OFF position

4.

Put remote selector in ON

 

 

(Remote-Ready Models Only)

 

position

 

5.

Wire disconnected from gas

5.

See Wiring Diagram, page 33

 

 

control (Remote-Ready Mod-

 

 

 

 

els Only)

 

 

 

 

 

 

Delayed ignition of one or both

1. Manifold pressure is too low

1.

Contact local natural or pro-

burners

2.

Burner orifice(s) clogged

 

pane/LP gas company

 

2.

Clean burner(s) (see Cleaning

 

 

 

 

and Maintenance, page 28) or

 

3.

Mislocated crossover tube

 

replace burner orifice(s)

 

3.

Contact qualified service

 

 

 

 

person

30

www.desatech.com

115254-01A

Page 30
Image 30
Desa LEN) (V)L32(HP, LZPR), LHP) (V)L36(EP, LEP) (V)L36(ZNR, LHN) (V)L36(EN Continued, ODS/pilot lights but flame goes