CHECKING GAS CONNECTIONS

INSTALLATION

Continued

We recommend that you install a sediment trap in supply line as shown in Figures 21 and 22, depend- ing on your model. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and heater. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.

Manual background CAUTION: Avoid damage to regulator. Hold gas regulator with wrench when connecting it to gas piping and/or fittings (Variable Manually-Controlled Models Only).

Manual background CAUTION: Avoid damage to gas control. Hold gas control with wrench when connecting it to gas piping and/or fittings (Remote-Ready Models Only).

 

 

CSA Design-

 

 

 

Certified Equipment

Propane/LP

Shutoff Valve with

1/8" NPT Tap*

Approved

From External

 

 

 

 

Flexible

Regulator

 

 

 

 

 

 

Gas Hose (if

(11" W.C.**

 

 

 

 

 

 

allowed by

to 14" W.C.

 

 

 

 

 

 

local codes)

Pressure)

 

 

 

 

 

 

 

Natural

 

 

 

 

From Gas

 

 

 

 

Meter (5"

 

 

 

 

W.C.** to

 

 

3" Minimum

10.5" W.C.

 

 

Tee Cap

Pipe

Gas

Pressure)

Regulator

 

Joint

Nipple

 

 

 

 

Sediment Trap

 

Figure 21 - Attaching Flexible Gas Line to

Control Valve (Manually-Controlled Models)

CSA Design-Certified Equipment Shutoff Valve with 1/8" NPT Tap*

Approved

Propane/LP

Flexible

- From External

Gas Hose (if

Regulator

allowed by

(11" W.C.** to 14"

local codes)

W.C. Pressure)

 

 

Natural - From

 

Gas Meter (5"

3" Minimum

W.C.** to 10.5"

 

Pipe

Cap TeeW.C. Pressure)

 

Nipple

Joint

Gas

Sediment Trap

Control

 

 

Figure 22 - Attaching Flexible Gas Line to Control Valve (Remote-Ready Models)

*Purchase the optional CSA design-certified equipment shutoff valve from your dealer. See Accessories, page 35.

**Minimum inlet pressure for purpose of input adjustment

CHECKING GAS CONNECTIONS

Manual background WARNING: Test all gas piping and connections, internal and external to unit, for leaks after installing or servicing. Correct all leaks at once.

Manual background WARNING: Never use an open flame to check for a leak. Apply a noncorrosive leak detec- tion fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

Manual background CAUTION: Make sure exter- nal regulator has been installed between propane/LP supply and heater.SeeguidelinesunderCon- necting to Gas Supply, page 16.