
SECTION 2 - WIRING
Before attempting to connect any wiring to the operator, be sure that the circuit breaker in the electrical panel is in the OFF position. Permanent wiring must be installed to the operator as required by local electrical codes. It is recommended that a licensed electrical contractor perform this work.
Since building codes vary from city to city, we highly recommend that you check with your local building department prior to installing any permanent wiring to be sure that all wiring to the operator (both high and low voltage) complies with local code requirements.
THIS GATE OPERATOR MUST BE PROPERLY GROUNDED!!2.1 High Voltage Wire Runs
The distance shown in the chart is measured in “Feet” from the operator to the power source. If power wiring is greater than the maximum distance shown, it is recommended that a service feeder be installed. When large gauge wire is used, a separate junction box must be installed for the operator connection. The wire table is based on stranded copper wire. Wire run calculations are based on a 110 VAC power source with a 3% voltage drop on the power line, plus an additional 10% reduction in distance to allow for other losses in the system.
This table illustrates the high voltage wire size and distance requirements.
Model Type | Amps Required |
| Wire Size / Distance in Feet |
| |
12 AWG | 10 AWG | 8 AWG | 6 AWG | ||
6050 Single | 4.3 | 215 | 345 | 575 | 890 |
6050 Dual | 8.6 | 105 | 170 | 285 | 430 |
|
|
|
|
|
|
6100 Single | 5.4 | 170 | 275 | 460 | 685 |
|
|
|
|
|
|
6100 Dual | 10.8 | 85 | 135 | 230 | 340 |
|
|
|
|
|
|
2.2 High Voltage Terminal Connection
DANGER | 115 VAC | |
HIGH VOLTAGE! | Neutral | 115 VAC |
| ||
Chassis |
|
|
Ground |
|
|
High Voltage
Conduit
•Route incoming high voltage power through conduit and into the operator as shown.
•Be sure wiring is installed in accordance with local codes. Be sure to color code all wiring.
•It is recommended that a surge suppressor be installed on the high voltage power lines to help protect the operator and circuit board from surges and power fluctuations.
•Secondary operator in a dual operator application gets power through the
Section 1 MUST be completed before power can be turned on.
16 |