Symptom

Possible Solution(s)

 

 

Gate opens a short

Check that the clutch is adjusted properly and is not slipping.

distance, then stops

Disconnect the gate from the gate operator and check that the gate swings freely without any binding.

and reverses.

Check that SW-1, switch 7 is set correctly.

 

Check the PULSE LED on the circuit board. PULSE 1 should blink as the primary (or single) operator

 

is running. PULSE 2 should blink as the secondary operator is running. If either PULSE LED is not

 

blinking as the respective operator is running, check that the magnetic sensor is within 1/32 inch of

 

the magnetic counter ring.

 

Replace the magnetic sensor.

 

Replace the circuit board.

Gate opens but will

Check the input LEDs. Any ON will hold the gate open and indicates a problem with a keying device.

not close.

Check the secondary safety devices. Any activated will hold the gate open and indicates a problem

 

with the safety device.

 

Check the loop detectors. Any activated can hold the gate open and indicates a problem with the

 

loop detector or ground loop.

 

Operator may be in a “soft shutdown.” Activate any keying device to determine if operator returns

 

to normal operation.

 

If automatic close is desired, be sure SW-1, switch 4 is ON.

 

Check motor as described on previous page.

 

 

Gate closes but will

Operator may be in a “soft shutdown.” Check input LEDs on terminals 11-13. If any are ON,

momentarily disconnect, then re-connect the wire going to the respective terminal. Operator should

not open.

open.

 

 

Check to be sure that the operator is running in the proper direction. Turn power OFF, and then back

 

ON. Activate a keying device. Operator should run in the open direction. If operator runs in the

 

close direction, turn power OFF and change direction switch SW-2, switches 1 and/or 2. Go to

 

above section if operator now opens but will not close.

 

Be sure that the respective LED on the control board lights when the keying device connected to the

 

respective terminal is activated. If LED does not light, momentarily place a jumper wire from

 

terminal 20 to the input terminal being checked. If LED lights and gate opens, problem is with the

 

keying device. If LED does not light, replace control board.

 

Check motor as described on previous page.

Gate starts to close,

Check that the clutch is adjusted properly and is not slipping.

Disconnect the gate from the operator and check that the gate operates freely without any binding.

then reverses to

Check the loop detector LEDs and input LEDs. Any that flash ON will cause the gate to reverse.

open.

If a shadow loop is used, check for proper wiring. A mis-wired shadow loop detector will cause the

 

 

gate to reverse.

 

Check the PULSE LED on the circuit board. PULSE 1 should blink as the primary (or single) operator

 

is running. PULSE 2 should blink as the secondary operator is running. If either PULSE LED is not

 

blinking as the respective operator is running, check that the magnetic sensor is within 1/32 inch of

 

the magnetic counter ring.

 

Replace the magnetic sensor.

 

Replace the circuit board.

Gate closes and then

Check for any input or loop detector LEDs that are ON.

re-opens.

Check that the operator is running in the proper direction (see “gate closes but will not open” above).

 

Check that SW-1, switch 5 is set correctly.

Alarm sounds for 5

 

minutes and then

Operator is in a “hard shutdown” condition. Reset switch must be activated to return operator to

beeps once every 5

normal operation.

seconds. Operator

 

will not run.

 

DC open system will

Check if the DC system is set to open gate automatically or requires an input to open.

not open gate upon

Check that the DC system power switch is in the ON position.

AC power outage.

Check the batteries for proper voltage. Replace if necessary.

 

Replace the DC system circuit board.

 

 

34

6050-065-L-11-08