To connect the transmitter

March 2013

Quick Installation Guide

To connect the transmitter

1.Verify that the power supply is disconnected.

2.Remove the terminal block cover (see picture below).

3.Pull the cable through the cable gland/conduit. For Explosion-proof / Flameproof installations, only use cable glands or conduit entry devices certified Explosion-proof or Flameproof. Install wiring with a drip loop where the bottom of the loop must be lower than the cable/conduit entry.

4.To connect the wires, see the illustrations on the following pages.

5.Use the enclosed metal plug to seal any unused port.

6.Tighten the cable gland.

7.Mount the cover and make sure it is fully engaged to meet Explosion-proof requirements (adapters are required if M20 glands are used).

For ATEX, IECEx, NEPSI, INMETRO, and TIIS installations, lock the cover with the locking screw.

8.Connect the power supply.

NOTE:

Use PTFE tape or other sealant at the NPT threads in the Cable Entries.

Terminal block

Terminal

Block

Cover

Cable Entry, ½ in. NPT - 14 or M20x1.5 adapter

External Ground Screw

Remove the orange, protective,

 

plastic plugs, used for

 

transportation.

 

Seal any unused port with the

 

enclosed metal plug.

Terminals for signal and power supply

Cable Entry, ½ in. NPT - 14 or M20x1.5 adapter

Internal Ground Screw

Locking screw

9