IC1 FOUNDATION fieldbus FISCO model:

Quick Installation Guide

March 2013

 

 

IC1 FOUNDATION fieldbus FISCO model:

Ex ia IIC T4 (-50 °C < Ta< +60 °C) DIP A20 TA69 °C

Ui = 17.5 V, Ii = 380 mA, Pi = 5.32 W, Ci = 4.95 nF, Li < 0.1 μH

N3 Type n:

HART model:

Ex nL IIC T4 (-50 °C < Ta < +70 °C)

Ui = 30 V, Ii = 130 mA, Pi = 1.0 W, Ci = 7.26 nF, Li = 0 μH

FOUNDATION fieldbus model:

Ex nL IIC T4 (-50 °C < Ta < +60 °C)

Ui = 30 V, Ii = 300 mA, Pi = 1.5 W, Ci = 4.95 nF, Li = 0 μH

Japanese certifications

Technology Institution of Industrial Safety (TIIS) approval

Special conditions for safe use (X):

Refer to certificate TC20104 and TC20192.

E41 Flameproof:

4-20 mA/HART model: Transmitter: Ex d [ia] IIC T4x -20 ~ +60 °C

DC 20 - 42.4 V

Um = 250 V Uo = 22.2 V Io = 177.5 mA

Po = 0.985 W Probe: Ex Ia IIC T4X

FOUNDATION fieldbus model: Transmitter: Ex d [ia] IIC T4X -20 ~ +60 °C

DC 16 - 32 V

Um = 250 V Uo = 22.2 V Io = 177.5 mA

Po = 0.985 W Probe: Ex ia IIC T4X

Installation Drawing: 05300-00548.

Approval valid for HART and FOUNDATION fieldbus options.

1)Ordering information code for Product Certifications, see the Rosemount 5300 Series Product Data Sheet (Document No. 00813-0100-4530) or the Rosemount 5300 Series Reference Manual

(Document No. 00809-0100-4530)