Brazilian certifications
INMETRO approvals
Special conditions for safe use (X)
Letter X in the number of the certificate indicates the following special condition(s) for safe use:
For models 530xFxxxxxxxxxE1..., 530xFxxxxxxxxxKA..., 530xFxxxxxxxxxKB... or 530xFxxxxxxxxxKC... and when the sensor area requires an EPL Ga, the installation of the transmitter on the process wall must be done in a way that ensures the minimum degree of protection IP67 in the connection, in compliance with regulation ABNT NBR IEC 60529.
The intrinsically safe circuit did not withstand the dielectric rigidity tests with 500 Vca as specified in clause 6.4.12 of regulation IEC
Probes covered with plastic or plastic discs should have a
This equipment contains light metals. The equipment must be installed in a way that the risk of impact or friction with other metal surfaces is eliminated.
The Ex ia version of the field device of model FISCO 5300 can be provided with a FISCO [Ex ib] power supply when the power supply is certified with three current limiter safety devices separately and with limitation of voltage, complying with the requirements of the Ex ia model.
Certificate: NCC 4205/07X
Standards:
ABNT NBR IEC:
E21 Flameproof:
FOUNDATION fieldbus model: Ex d ia IIC T4 Gb/Ga Ex ta IIIC T69 °C
MODBUS model:
Ex d ia IIC T4 Gb/Ga Ex ta IIIC T79 °C
1)Ordering information code for Product Certifications, see the Rosemount 5300 Series Product Data Sheet (Document No.