Emerson 00825-0100-4530 Rev EC manual FOUNDATION fieldbus parameters

Models: 00825-0100-4530 Rev EC

1 36
Download 36 pages 54.13 Kb
Page 17
Image 17
FOUNDATION fieldbus parameters:

March 2013

Quick Installation Guide

are normally configured at the factory, but can be changed if, for example, the probe is cut in the field, or if disturbing objects in the near zone need to be blocked out (Hold Off Distance/Upper Null Zone (UNZ)).

Handheld HART Communicator: Fast Key Sequence [2, 1, 2].

FOUNDATION fieldbus parameters:

TRANSDUCER_1100 > PROBE_TYPE

TRANSDUCER_1100 > PROBE_LENGTH

TRANSDUCER_1100 > GEOM_HOLD_OFF_DIST

Click Next and the following window appears (Geometry).

7.Enter Tank Height, the distance from the Upper Reference Point to the Lower Reference Point (which is the tank bottom in the screenshot above), making sure it is as accurate as possible. See Configuration in the Rosemount 5300 Series Reference Manual (Document No. 00809-0100-4530) for details.

Set Mounting Type. Set Diameter if Mounting Type is Nozzle or Pipe/Chamber. Set Nozzle Height if Mounting Type is Nozzle.

Handheld HART Communicator: Fast Key Sequence [2, 1, 3]

FOUNDATION fieldbus parameters:

TRANSDUCER_1100 > GEOM_TANK_HEIGHT

TRANSDUCER_1100 > MOUNTING_TYPE

TRANSDUCER_1100 > PIPE_DIAMETER

TRANSDUCER_1100 > NOZZLE_HEIGHT

17

Page 17
Image 17
Emerson 00825-0100-4530 Rev EC manual FOUNDATION fieldbus parameters