Quick Installation Guide

March 2013

 

 

Click Next and the following window appears (Tank Environment).

8.In the Environment window, select Measurement Mode. If the surface is moving up or down at rates over 40 mm/s (1.5 in./s), the Rapid Level Changes box should also be selected. Enter the Upper Product Dielectric Constant (icons for help functions are available to the right). For Interface Level with Submerged Probe and Product and Interface measurement modes, it is important that the dielectric constant value is exact.

See the Rosemount 5300 Series Reference Manual (Document No. 00809-0100-4530) for details.

Handheld HART Communicator: Fast Key Sequence [2, 1, 4]

FOUNDATION fieldbus parameters:

TRANSDUCER_1100 > MEAS_MODE

TRANSDUCER_1100 > PRODUCT_DIELEC_RANGE

TRANSDUCER_1100 > UPPER_PRODUCT_DC

TRANSDUCER_1100 > ENV_ENVIRONMENT

Click Next and the following window appears (Volume).

9.If volume calculation is desired, choose a pre-defined Volume Calculation Method and tank dimensions based on a tank shape that corresponds to the actual tank. Choose Strapping Table if the actual tank does not match any of

18