Emerson 00825-0100-4530 Rev EC manual FOUNDATION fieldbus parameters

Models: 00825-0100-4530 Rev EC

1 36
Download 36 pages 54.13 Kb
Page 19
Image 19
Manual background

March 2013

Quick Installation Guide

the available pre-defined tank options, or if high volume accuracy is desired. Choose None if volume calculation is not desired.

Handheld HART Communicator: Fast Key Sequence [2, 1, 5]

FOUNDATION fieldbus parameters:

TRANSDUCER_1300 > VOL_VOLUME_CALC_METHOD

TRANSDUCER_1300 > VOL_IDEAL_DIAMETER

TRANSDUCER_1300 > VOL_IDEAL_LENGTH

TRANSDUCER_1300 > VOL_VOLUME_OFFSET

Click Next and the following window appears (Analog Output).

NOTE:

The 4-20 mA range must not include the upper transition zone, the lower transition zone, or the upper null zone. See the Rosemount 5300 Series Reference Manual (Document No. 00809-0100-4530) for details.

10.This step is not applicable for FOUNDATION fieldbus, the parameters are entered in the AI-block instead.

Handheld HART Communicator: Fast Key Sequence [2, 1, 6]

For HART communication, choose Primary Variable, PV.

Specify the analog output range by setting the Upper Range Value (20 mA) and the Lower Range Value (4 mA) to the desired corresponding level values. The Alarm Mode specifies the output state when a measurement error occurs. Choose between the following:

High: 21.75 mA (standard) or 22.5 mA (Namur)

Low: 3.75 mA (standard) or 3.6 mA (Namur)

Freeze: the output current is set to the last valid value at the time when the error occurs.

Click Next.

11.Continue with Steps 2 to 5 in the Guided Setup window:

Step 2: Device specific setup might advise you to make further configurations.

Handheld HART Communicator: Fast Key Sequence [2, 1, 7, 2].

Step 3: Restart the device to make sure all configuration changes are properly activated.

Step 4: View live values from the device to verify that the transmitter works correctly.

Step 5: Make a complete backup of the device.