Operation

10.2.1Startup Procedure

To start the UPS from a fully powered-down condition:

1.Open the external power switch.

2.Open the UPS door.

3.Connect the power supply cables.

4.Ensure the correct phase rotation.

5.Confirm that the address DIP switch of the main Liebert FlexPower assemblies are different from each other, and they are within 1 to 6. If they are the same, adjust them to create different Liebert FlexPower assembly addresses.

Table 29 Dip switch matrix

FlexPower Assembly Address

Flex Power

 

Swtich Number Left to Right

 

Assembly

 

 

 

 

 

 

 

1

 

2

3

4

 

5

Address Top to Bottom

 

 

 

 

 

 

 

 

 

 

6

Down

 

Up

Up

Down

 

Down

 

 

 

 

 

 

 

 

5

Up

 

Down

Up

Down

 

Down

 

 

 

 

 

 

 

 

4

Down

 

Down

Up

Down

 

Down

 

 

 

 

 

 

 

 

3

Up

 

Up

Down

Down

 

Down

 

 

 

 

 

 

 

 

2

Down

 

Up

Down

Down

 

Down

 

 

 

 

 

 

 

 

1

Up

 

Down

Down

Down

 

Down

 

 

 

 

 

 

 

 

NOTE

For standardization, if the quantity of modules in system is less than 6, for example 45kVA system, Emerson recommends setting the address bits of the modules as 1, 2, 3 respectively.

6.Close the external input circuit breaker and connect input power.

The LCD activates. The rectifier indicator flashes while the rectifier is starting. The rectifier enters normal operation state, and after about 30 seconds, the rectifier indicator stops blinking and is illuminated in a steady green. After initialization, the bypass static switch turns on. The mimic LEDs appear as shown Table 30.

Table 30 Mimic indicators after initialization

LED

Status

 

 

Rectifier Indicator

Green

Battery Indicator

Red

Bypass Indicator

Green

Inverter Indicator

Off

Load Indicator

Green

Status Indicator

Amber

7.Ensure that the Liebert FlexPower assembly ready switches are latched (in Down position).

8.Close the external output circuit breaker.

9.Press the INVERTER ON button for 2 seconds. The inverter indicator flashes while the inverter is starting. After the inverter is ready, the UPS transfers from bypass to inverter, the bypass indicator turns Off, and the inverter indicator turns On. The UPS is in Normal Mode. The mimic LEDs will appear as shown below.

91

Page 101
Image 101
Emerson 115-480 Startup Procedure, Dip switch matrix, Mimic indicators after initialization, FlexPower Assembly Address

115-600V, 115-208, 115-120, 115-50/60HZ, 115-480 specifications

The Emerson 15-90KVA series is a robust and versatile power solution designed for various applications including commercial, industrial, and data center operations. Operating at voltage ranging from 115 to 480 volts, and supporting frequencies of either 50 or 60 Hz, this series is engineered to meet diverse power requirements.

One of the standout features of the Emerson 15-90KVA is its exceptional reliability and performance under varying load conditions. This power system incorporates cutting-edge technologies that enhance operational efficiency while minimizing downtime. The robust design of the system enables it to maintain optimal performance even in harsh environmental conditions, providing power continuity and safeguarding critical operations.

The Emerson 15-90KVA is equipped with advanced protection mechanisms that ensure the safety of connected equipment. These include overload protection, short-circuit protection, and thermal protection systems, which work together to prevent potential damage from power surges or faults. Moreover, the unit features a user-friendly interface that facilitates easy monitoring and control, enabling operators to track performance metrics and manage power supply effectively.

Another significant characteristic of this power series is its modular design, allowing for scalability and flexibility. Users can easily add or remove capacity based on changing power demands without the need for extensive system overhauls. This scalability makes the Emerson 15-90KVA ideal for growing businesses that require adaptable power solutions.

Energy efficiency is a focal point for the Emerson power series. Utilizing advanced power electronics and intelligent control algorithms, the system minimizes energy losses, ensuring that more power is available for direct usage. This not only reduces operational costs but also aligns with growing sustainability initiatives by lowering the overall carbon footprint.

In summary, the Emerson 15-90KVA series is a high-performance power solution characterized by its reliability, advanced protection features, modular scalability, and energy efficiency. Its versatility across multiple voltage levels and frequency options makes it suitable for a wide range of applications, solidifying its position as a preferred choice in the industry. Whether for industrial facilities, data centers, or commercial spaces, the Emerson 15-90KVA is designed to meet and exceed power demands effectively and efficiently.