Maintenance

APPENDIX B UPS STATUS MESSAGES

Table 57 shows all event messages as they appear in the current status area of the LCD or the history log, along with a description and recommended actions, if any. For further information on the current status area and the history log, see 9.10 - UPS History Log.

Table 57 UPS status messages

Event Message

Description / Suggested Action (if any)

 

 

Comm. Fail

The CAN communication between internal monitor and rectifier/inverter/bypass fails. Contact

Liebert Services at 800-543-2378 for assistance.

 

Battery Overtemp.

The Battery temperature is over limit. Check the battery temperature and ventilation.

 

 

Ambient Overtemp.

The Ambient temperature is over limit. Check the ventilation of UPS room.

 

 

Replace Battery

Battery should be replaced. Contact Liebert Services at 800-543-2378 for assistance.

 

 

 

Before the end of discharging, battery under-voltage pre-warning should occur. After this pre-

Battery Low Pre-warning

warning, battery should have the capacity for 3 minutes discharging with full load. The time is

user configured from 3 to 60 minutes.

 

 

Shut down the load in time.

 

 

Battery End of Discharge

Inverter turned off due to low battery voltage.

Check the utility failure and try to fix it.

 

Mains Volt. Abnormal

Mains Voltage exceeds the upper or lower limit and results in rectifier shutdown.

Check the input line-to-neutral voltage amplitude of rectifier.

 

Mains Undervoltage

Mains Voltage is undervoltage (120v~132V).

Check the input line-to-line voltage amplitude of rectifier.

 

Mains Freq. Abnormal

Mains frequency is out of limit range and results in rectifier shutdown.

Check the rectifier’s input voltage frequency.

 

Rectifier Fault

Rectifier Fault; Contact Liebert Services at 800-543-2378 for assistance.

 

 

Rectifier Overtemp.

The temperature of heat sink is too high to keep the rectifier running.

The UPS can recover automatically. Check the environment and ventilation.

 

Charger Fault

The Charger has failed. Contact Liebert Services at 800-543-2378 for assistance.

 

 

Input Fuse Fail

Input fuse is open. Contact Liebert Services at 800-543-2378 for assistance.

 

 

Control Power 1 Fail

Control Power 1 has failed or has been lost. Contact Liebert Services at 800-543-2378 for

assistance.

 

Mains Phase Reversed

Input phase sequence is reversed. Contact Liebert Services at 800-543-2378 for assistance.

 

 

Soft Start Fail

Rectifier could not start due to low DC bus voltage. Contact Liebert Services at 800-543-2378 for

assistance.

 

 

This alarm is triggered by an inverter software routine when the amplitude or frequency of bypass

 

voltage is beyond the normal range.

 

The amplitude threshold is fixed for positive and negative 10% rating.

 

This alarm automatically resets once the bypass voltage goes normal.

Bypass Unable to Trace

1. First verify that the bypass voltage and frequency displayed on the panel is within the selected

range. Note here the rated voltage and frequency are specified by “Output voltage level” and

 

 

“Output frequency level” respectively.

 

2. If the displayed voltage is believed to be abnormal, then verify the bypass voltage and

 

frequency presented to the UPS. Check the external supply if it is found to be faulty.

 

Contact Liebert Services at 800-543-2378 for assistance.

 

This alarm is triggered by an inverter software routine when the amplitude or frequency of bypass

 

voltage exceeds the limit.

 

This alarm automatically resets once the bypass voltage goes normal.

 

First check if there are some relevant alarms such as “Bypass disconnect open”, “Bypass phase

 

reverse” and “Mains neutral lost”. If they appear, solve them first.

Bypass Abnormal

1. Then verify that the bypass voltage and frequency displayed on the panel is within the bypass

limit. Note here the rated voltage and frequency are specified by “Output voltage level” and

 

“Output frequency level” respectively.

 

2. If the displayed voltage is believed to be abnormal, then verify the bypass voltage and

 

frequency presented to the UPS. Check the external bypass supply if it is found to be faulty. If

 

the utility is likely to trigger this alarm frequently, the bypass limit can be changed a little larger

 

through the configuration software according to the customer’s agreement.

 

Contact Liebert Services at 800-543-2378 for assistance.

117

Page 127
Image 127
Emerson 15-90KVA, 115-120, 115-208, 115-50/60HZ UPS status messages, Event Message Description / Suggested Action if any

115-600V, 115-208, 115-120, 115-50/60HZ, 115-480 specifications

The Emerson 15-90KVA series is a robust and versatile power solution designed for various applications including commercial, industrial, and data center operations. Operating at voltage ranging from 115 to 480 volts, and supporting frequencies of either 50 or 60 Hz, this series is engineered to meet diverse power requirements.

One of the standout features of the Emerson 15-90KVA is its exceptional reliability and performance under varying load conditions. This power system incorporates cutting-edge technologies that enhance operational efficiency while minimizing downtime. The robust design of the system enables it to maintain optimal performance even in harsh environmental conditions, providing power continuity and safeguarding critical operations.

The Emerson 15-90KVA is equipped with advanced protection mechanisms that ensure the safety of connected equipment. These include overload protection, short-circuit protection, and thermal protection systems, which work together to prevent potential damage from power surges or faults. Moreover, the unit features a user-friendly interface that facilitates easy monitoring and control, enabling operators to track performance metrics and manage power supply effectively.

Another significant characteristic of this power series is its modular design, allowing for scalability and flexibility. Users can easily add or remove capacity based on changing power demands without the need for extensive system overhauls. This scalability makes the Emerson 15-90KVA ideal for growing businesses that require adaptable power solutions.

Energy efficiency is a focal point for the Emerson power series. Utilizing advanced power electronics and intelligent control algorithms, the system minimizes energy losses, ensuring that more power is available for direct usage. This not only reduces operational costs but also aligns with growing sustainability initiatives by lowering the overall carbon footprint.

In summary, the Emerson 15-90KVA series is a high-performance power solution characterized by its reliability, advanced protection features, modular scalability, and energy efficiency. Its versatility across multiple voltage levels and frequency options makes it suitable for a wide range of applications, solidifying its position as a preferred choice in the industry. Whether for industrial facilities, data centers, or commercial spaces, the Emerson 15-90KVA is designed to meet and exceed power demands effectively and efficiently.