Maintenance

Table 57 UPS status messages (continued)

Event Message

Description / Suggested Action (if any)

 

 

 

This alarm is triggered by an inverter software routine when the inverter and bypass waveforms

 

are misaligned by more than 6 degrees in phase. This alarm resets automatically once the

 

condition is no longer true.

Inverter Asynchronous

1. First check if the alarm “Bypass unable to trace” or “Bypass abnormal” occurs. If so, solve it

first.

 

 

2. Verify the waveform of the bypass voltage. If it is too distorted, ask the customer to verify and

 

seek any possible measurements.

 

Contact Liebert Services at 800-543-2378 for assistance.

Inverter Fault

This alarm indicates a fault condition exists within the inverter.

Contact Liebert Services at 800-543-2378 for assistance.

 

Fan Fault

At least one of the cooling fans failed. Contact Liebert Services at 800-543-2378 for assistance.

Inverter STS (relay) Fail

At least one of the static switches of inverter side is open or short circuit. This fault is locked until

power off. Contact Liebert Services for assistance at 800-543-2378 for assistance.

 

 

At least one of the static switches of bypass side is open or short circuit. This fault is locked until

Bypass STS Fail

power off.

 

Contact Liebert Services at 800-543-2378 for assistance.

Output Fuse Fail

At least one of the output fuses is open. Contact Liebert Services at 800-543-2378 for assistance.

Control Power 2 Fail

Control Power 2 is abnormal or lost. Contact Liebert Services at 800-543-2378 for assistance.

 

 

 

The UPS is confirmed to be overload when the load arises above 105% nominal rating.

 

The alarm automatically resets once the overload condition is removed.

 

1. Confirm that the alarm is true by checking the load percent indicated on the LCD panel to

Unit Overload

determine which phase is being overloaded.

2. If the alarm is true, measure the actual output current to verify that the indications are valid.

 

 

Disconnect unnecessary load and ensure the safety. In a parallel system, a severe load

 

sharing error can also leads to the alarm.

 

Contact Liebert Services at 800-543-2378 for assistance.

 

The UPS parallel system is confirmed to overload when the total load arises above 105% nominal

 

rating for the set basic number of UPSs. The alarm automatically resets once the overload

 

condition is removed.

System Overload

1. Confirm that the alarm is true by checking the system load percent indicated on the LCD

panel to determine which phase is being overloaded.

 

 

2. If the alarm is true, measure the actual output current to verify that the indications are valid.

 

Disconnect unnecessary load and ensure the safety. In a parallel system, a severe load

 

sharing error can also leads to the alarm.

 

The UPS is confirmed to overload and the overload times out.

 

Note 1: The highest loaded phase will indicate overload timing-out first.

 

Note 2: When the timer is active, then alarm “unit overload” should also be active as the load is

 

above nominal.

 

Note 3: When the timer has expired, the inverter Static Switch is opened and the load transferred

Unit Overload Timeout

to bypass. The inverter shutdown and will restart after 10 seconds.

 

Note 4: If the load decreases lower than 95% after 5 minutes, the system will transfer back to

 

inverter mode.

 

Confirm that the alarm is genuine by checking the load percent indicated on the LCD. If an

 

overload is indicated then check the load, and investigate any additional load connected prior to

 

the alarm (if applicable).

 

The phase sequence direction of bypass voltage is reversed.

 

Normally, the phase of Phase B lags 120 degrees behind Phase A, and the phase of Phase C

Bypass Phase Reversed

lags 120 degrees behind Phase B.

 

Verify that the phase rotation of the bypass supply presented to the UPS is correct, and rectify it if

 

it is found to be in error. Contact Liebert Services at 800-543-2378 for assistance.

Load Impact Transfer

A transfer to bypass occurred due to a large step load. The UPS should recover automatically.

Turn on connected equipment in sequential order to reduce the step loading of the inverter.

 

 

The load is on bypass power due to excessive number of transfers that occurred within the last

Transfer Timeout

hour.

The UPS will recover automatically and will transfer the load back to inverter power within an

 

 

hour.

Load Sharing Fault

UPS working within a parallel system are not sharing load current correctly. Contact Liebert

Services at 800-543-2378 for assistance.

 

118

Page 128
Image 128
Emerson 115-208, 115-120, 15-90KVA, 115-50/60HZ, 115-600V, 115-480 user manual 118

115-600V, 115-208, 115-120, 115-50/60HZ, 115-480 specifications

The Emerson 15-90KVA series is a robust and versatile power solution designed for various applications including commercial, industrial, and data center operations. Operating at voltage ranging from 115 to 480 volts, and supporting frequencies of either 50 or 60 Hz, this series is engineered to meet diverse power requirements.

One of the standout features of the Emerson 15-90KVA is its exceptional reliability and performance under varying load conditions. This power system incorporates cutting-edge technologies that enhance operational efficiency while minimizing downtime. The robust design of the system enables it to maintain optimal performance even in harsh environmental conditions, providing power continuity and safeguarding critical operations.

The Emerson 15-90KVA is equipped with advanced protection mechanisms that ensure the safety of connected equipment. These include overload protection, short-circuit protection, and thermal protection systems, which work together to prevent potential damage from power surges or faults. Moreover, the unit features a user-friendly interface that facilitates easy monitoring and control, enabling operators to track performance metrics and manage power supply effectively.

Another significant characteristic of this power series is its modular design, allowing for scalability and flexibility. Users can easily add or remove capacity based on changing power demands without the need for extensive system overhauls. This scalability makes the Emerson 15-90KVA ideal for growing businesses that require adaptable power solutions.

Energy efficiency is a focal point for the Emerson power series. Utilizing advanced power electronics and intelligent control algorithms, the system minimizes energy losses, ensuring that more power is available for direct usage. This not only reduces operational costs but also aligns with growing sustainability initiatives by lowering the overall carbon footprint.

In summary, the Emerson 15-90KVA series is a high-performance power solution characterized by its reliability, advanced protection features, modular scalability, and energy efficiency. Its versatility across multiple voltage levels and frequency options makes it suitable for a wide range of applications, solidifying its position as a preferred choice in the industry. Whether for industrial facilities, data centers, or commercial spaces, the Emerson 15-90KVA is designed to meet and exceed power demands effectively and efficiently.