Specifications and Technical Data

Table 44 UPS currents and terminals—Output 208V

 

 

 

 

 

 

Maximum Recommended Lug (T&B)

 

 

 

 

 

 

 

 

 

Nominal

 

 

 

 

Compression

Mechanical

Unit

Output

OCP Device

 

75°C Wire

 

Lug Two Hole

Lug Two Hole

Rating

Current

Rating

Bolt Size

Current, tot

Wire

3/8" Bolt

3/8" Bolt

15

42

70

M10 (3/8")

130

(1) #1

54857BE

32209

 

 

 

 

 

 

 

 

30

83

150

M10 (3/8")

150

(1) 1/0

54860BE

32209

 

 

 

 

 

 

 

 

45

125

200

M10 (3/8")

175

(1) 2/0

54862BE

32209

 

 

 

 

 

 

 

 

60

167

300

M10 (3/8")

230

(1) 4/0

54866BE

32211

 

 

 

 

 

 

 

 

75

208

350

M10 (3/8")

300

(2) 1/0

54860BE

32209

 

 

 

 

 

 

 

 

90

250

400

M10 (3/8")

350

(2) 2/0

54862BE

32209

 

 

 

 

 

 

 

 

Table 45 UPS currents and terminals—Battery (288V string)

 

 

 

 

 

 

Maximum Recommended Lug (T&B)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compression

Mechanical

Unit

Battery

OCP Device

 

75°C Wire

 

Lug Two Hole

Lug Two Hole

Rating

Current

Rating

Bolt Size

Current, tot

Wire

3/8" Bolt

3/8" Bolt

15

67

80

M10 (3/8")

130

(1) #1

54857BE

32209

 

 

 

 

 

 

 

 

30

135

150

M10 (3/8")

175

(1) 2/0

54862BE

32209

 

 

 

 

 

 

 

 

45

202

225

M10 (3/8")

230

(1) 4/0

54866BE

32211

 

 

 

 

 

 

 

 

60

269

300

M10 (3/8")

300

(2) 1/0

54860BE

32209

 

 

 

 

 

 

 

 

75

336

350

M10 (3/8")

400

(2) 3/0

54864BE

32211

 

 

 

 

 

 

 

 

90

404

450

M10 (3/8")

460

(2) 4/0

54866BE

32211

 

 

 

 

 

 

 

 

Table 46 AC/AC efficiency, loss and air exchange

AC/AC Efficiency

 

 

 

 

Data

 

 

Normal mode (dual conversion), %

 

 

 

94 maximum

 

 

Inverter Efficiency (DC/AC) (battery at nominal voltage 288VDC and full-rated linear load)

 

 

Rated Power, kVA

 

 

 

 

15-90

 

 

 

Battery Mode, %

 

 

 

 

94

 

 

 

Heat Losses & Air Exchange

 

 

 

 

 

 

 

 

 

Rated Power, kVA

15

30

 

45

 

60

 

75

90

Normal Mode, kW

0.9

1.8

 

2.7

 

3.6

 

4.5

5.4

No Load, kW

0.3

0.6

 

0.9

 

1.2

 

1.5

1.8

Maximum forced air cooling

102 (173)

204 (346)

 

306 (519)

 

408 (692)

 

510 (865)

612 (1038)

(front intake, rear exhaust), L/sec (m3/hr)

 

 

 

Heat Dissipation, BTU/Hr (kWH)

 

 

 

 

 

 

 

 

 

Without Transformer

3074 (0.9)

6147 (1.8)

 

9220 (2.7)

 

12295 (3.6)

 

15368 (4.5)

18442 (5.4)

With Transformer, 480V

13928 (4)

17001 (5)

 

20074

 

23149 (6.8)

 

26222 (7.8)

29296 (8.6)

 

(5.9)

 

 

 

 

 

 

 

 

 

 

 

With Transformer, 600V

13726 (4)

16772

 

19845

 

22920 (6.7)

 

25993 (7.6)

29067 (8.5)

(4.9)

 

(5.8)

 

 

 

 

 

 

 

 

 

 

Top Fan Maximum Forced Air Cooling: 467 L/sec

(1680 m3/hr) total for 2 fans

 

 

 

 

 

 