Specifications and Technical Data

Table 49 Inverter output to critical load

Parameter

15 - 90kVA

Rated AC Voltage 1

208/120, 220/127VAC, 60Hz, 3-phase, 3- or 4-wire plus ground

Frequency 2

60Hz

 

110% load, 60 min

Overload Capacity

125% load, 10 min

 

150% load, 60 sec

Fault Current

Short circuit for 200 ms

 

 

Non-Linear Load Capability 3

100%

Neutral Current Capability

170%

 

 

Steady State Voltage Stability

±1% (balanced load)

 

 

Voltage Regulation

±1% for balanced load

±5% for 100% unbalanced load

 

Phase Balance

120° ±1° for balanced load

120° ±15°± for 100 unbalanced load

 

Transient Voltage Response 4

±5%

THD

< 1% (linear load), <4% (non linear load 3)

Sync Frequency Range

Rated frequency ± 2Hz (selectable ± 0.5 to ± 3Hz)

 

 

Frequency Slew Rate

0.2 to 3Hz/sec

 

 

Frequency Regulation

±0.1% (single Liebert FlexPower Assembly)

±0.25% (six Liebert FlexPower Assemblies)

 

Voltage Adjustment Range

±5%

 

 

1.Factory set to 208V or 220V selectable by commissioning engineer.

2.Factory set to 60Hz; 50Hz selectable by commissioning engineer. Frequency converter operation also selectable.

3.EN50091-3 (1.4.58) crest factor: 3:1

4.IEC62040-3/ EN 50091-3 also for 0-100-0% load transient. Transient recovery time: return to within 5% of steady state output voltage within half a cycle.

5.Three-phase, 4 wire and shared neutral with the bypass input.

Table 50 Bypass input

Parameter

 

15 - 90kVA

 

 

 

Rated AC Voltage 1 2

 

208/220V 3-phase

Rated current

 

208V

252A

 

220V

240A

 

 

 

 

 

Overload

 

135% load, long term

Upstream protection, bypass line

 

Thermomagnetic circuit-breaker, rated up to 125% of nominal output

 

current. IEC 60947-2 curve C.

 

 

 

Current rating of neutral cable, A

 

1.7×In

Frequency, Hz

 

60

Transfer time between Bypass and Inverter, ms

Synchronous transfer: 0ms

Asynchronous transfer (default): 15 ms (50 Hz), 13.3 ms (60 Hz)

 

 

 

or 40, 60, 80, 100 ms selectable

Bypass voltage tolerance,%VAC

 

Upper limit: +10, +15 or +20, default +15

 

Lower limit: -10, -20, -30 or -40; default: -20 (delay time to accept steady

 

 

 

bypass voltage: 10 sec)

Bypass frequency tolerance,%

 

±10 or ±20; default ±10

Synchronization - Window

 

Rated frequency ± 2Hz (selectable ± 0.5 to ± 3Hz)

1.Factory-set to 208 or 220V selectable by commissioning engineer.

2.Three-phase, 4 wire and shared neutral with the rectifier input. Neutral referenced to the output.

109

Page 119
Image 119
Emerson 115-480, 115-120, 15-90KVA, 115-208, 115-50/60HZ, 115-600V user manual Inverter output to critical load, Bypass input

115-600V, 115-208, 115-120, 115-50/60HZ, 115-480 specifications

The Emerson 15-90KVA series is a robust and versatile power solution designed for various applications including commercial, industrial, and data center operations. Operating at voltage ranging from 115 to 480 volts, and supporting frequencies of either 50 or 60 Hz, this series is engineered to meet diverse power requirements.

One of the standout features of the Emerson 15-90KVA is its exceptional reliability and performance under varying load conditions. This power system incorporates cutting-edge technologies that enhance operational efficiency while minimizing downtime. The robust design of the system enables it to maintain optimal performance even in harsh environmental conditions, providing power continuity and safeguarding critical operations.

The Emerson 15-90KVA is equipped with advanced protection mechanisms that ensure the safety of connected equipment. These include overload protection, short-circuit protection, and thermal protection systems, which work together to prevent potential damage from power surges or faults. Moreover, the unit features a user-friendly interface that facilitates easy monitoring and control, enabling operators to track performance metrics and manage power supply effectively.

Another significant characteristic of this power series is its modular design, allowing for scalability and flexibility. Users can easily add or remove capacity based on changing power demands without the need for extensive system overhauls. This scalability makes the Emerson 15-90KVA ideal for growing businesses that require adaptable power solutions.

Energy efficiency is a focal point for the Emerson power series. Utilizing advanced power electronics and intelligent control algorithms, the system minimizes energy losses, ensuring that more power is available for direct usage. This not only reduces operational costs but also aligns with growing sustainability initiatives by lowering the overall carbon footprint.

In summary, the Emerson 15-90KVA series is a high-performance power solution characterized by its reliability, advanced protection features, modular scalability, and energy efficiency. Its versatility across multiple voltage levels and frequency options makes it suitable for a wide range of applications, solidifying its position as a preferred choice in the industry. Whether for industrial facilities, data centers, or commercial spaces, the Emerson 15-90KVA is designed to meet and exceed power demands effectively and efficiently.