Ground Leakage Currents

! CAUTION

Risk of electric shock from high leakage current. Can cause injury, property damage and death.

EARTH CONNECTION IS ESSENTIAL BEFORE CONNECTING THE INPUT SUPPLY. Earth leakage current exceeds 3.5 mA and is less than 1000 mA.

Transient and steady-state earth leakage currents, which may occur when starting the equipment, should be taken into account when selecting instantaneous RCCB or RCD devices.

Residual Current Circuit Breakers (RCCBs) must be selected sensitive to DC unidirectional pulses (Class A) and insensitive to transient current pulses.

Note also that the earth leakage currents of the load will be carried by this RCCB or RCD. This equipment must be earthed in accordance with the local electrical code of practice.

! WARNING

Risk of electric shock. Can cause injury, property damage and death.

Under typical operation and with all UPS doors closed, only normal safety precautions are necessary. The area around the UPS system should be kept free of puddles of water, excess moisture and debris.

Special safety precautions are required for procedures involving handling, installation and maintenance of the UPS system and the internal batteries (internal batteries accommodated by 45kVA frame only). Observe all safety precautions in this manual before handling or installing the UPS system as well as during all maintenance procedures. Observe all battery safety precautions before working on or near the battery.

This equipment contains several circuits that are energized with high voltage. Only test equipment designed for troubleshooting should be used. This is particularly true for oscilloscopes. Always check with AC and DC voltmeters to ensure safety before making contact or using tools. Even when the power is turned Off, dangerously high electric charges may exist within the UPS.

All power and control wiring should be installed by a qualified electrician. All power and control wiring must comply with the NEC and applicable local codes.

ONLY qualified service personnel should perform maintenance on the UPS system.

When performing maintenance with any part of the equipment under power, service personnel and test equipment should be standing on rubber mats. The service personnel should wear insulating shoes for isolation from direct contact with the floor (earth ground).

Never work alone, even if all power is removed from the equipment. A second person should be standing by to assist and summon help in case an accident should occur.

NOTICE

Risk of improper ground connection. Can cause equipment damage.

Ground connection is essential before connecting the input supply. This equipment must be grounded in accordance with local electrical codes. Maximum load must not exceed that shown on the UPS rating label.

NOTICE

Risk of improper improper electromagnetic shielding. Can cause radio communication interference.

This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J of the FCC rules. These limits provide reasonable protection against harmful interference in a commercial environment. This unit generates, uses and radiates radio frequency energy and, if not installed and used in accordance with this instruction manual, may cause harmful interference to radio communications. This unit is not designed for use in a residential area. Operation of this unit in a residential area may cause harmful interference that the user is solely responsible for correcting.

2

Page 12
Image 12
Emerson 115-120, 15-90KVA, 115-208, 115-50/60HZ, 115-600V, 115-480 user manual Ground Leakage Currents

115-600V, 115-208, 115-120, 115-50/60HZ, 115-480 specifications

The Emerson 15-90KVA series is a robust and versatile power solution designed for various applications including commercial, industrial, and data center operations. Operating at voltage ranging from 115 to 480 volts, and supporting frequencies of either 50 or 60 Hz, this series is engineered to meet diverse power requirements.

One of the standout features of the Emerson 15-90KVA is its exceptional reliability and performance under varying load conditions. This power system incorporates cutting-edge technologies that enhance operational efficiency while minimizing downtime. The robust design of the system enables it to maintain optimal performance even in harsh environmental conditions, providing power continuity and safeguarding critical operations.

The Emerson 15-90KVA is equipped with advanced protection mechanisms that ensure the safety of connected equipment. These include overload protection, short-circuit protection, and thermal protection systems, which work together to prevent potential damage from power surges or faults. Moreover, the unit features a user-friendly interface that facilitates easy monitoring and control, enabling operators to track performance metrics and manage power supply effectively.

Another significant characteristic of this power series is its modular design, allowing for scalability and flexibility. Users can easily add or remove capacity based on changing power demands without the need for extensive system overhauls. This scalability makes the Emerson 15-90KVA ideal for growing businesses that require adaptable power solutions.

Energy efficiency is a focal point for the Emerson power series. Utilizing advanced power electronics and intelligent control algorithms, the system minimizes energy losses, ensuring that more power is available for direct usage. This not only reduces operational costs but also aligns with growing sustainability initiatives by lowering the overall carbon footprint.

In summary, the Emerson 15-90KVA series is a high-performance power solution characterized by its reliability, advanced protection features, modular scalability, and energy efficiency. Its versatility across multiple voltage levels and frequency options makes it suitable for a wide range of applications, solidifying its position as a preferred choice in the industry. Whether for industrial facilities, data centers, or commercial spaces, the Emerson 15-90KVA is designed to meet and exceed power demands effectively and efficiently.