Specifications and Technical Data

 

 

Table 47 Rectifier input

 

 

 

Parameter

15-90kVA

Rated AC Input Voltage 3

208/120V or 220/127V, 60Hz, 3-Phase, 4-Wire Plus Ground

Input Voltage Range, Startup/Operating

96-138V or 102-146V or -20%, +15% (Full Load)

Input Voltage Range, Operating

72-138V or 76-146V or -40%, +15% (<80% Load)

Frequency

50 or 60Hz (40-70Hz Range)

Power Factor

0.99 Full Load, 0.98 Half Load

Input Current, Rated 1

45/90/135/180/225/270 A

Input Current, Max 2

60/120/180/240/300/360 A

THD

3% THDI Full Load

1.At rated load and 208V input with battery charged (EN 62040-3 / 50091-3).

2.At rated load and 208V input with battery charging at maximum power (EN 62040-3 / 50091-3).

3.Three-phase, four-wire and shared neutral with the bypass input.

Table 48 Battery DC intermediate circuit

Parameter

 

15 - 90kVA

 

 

 

 

Battery Bus Voltage

Nominal: 288VDC (VRLA Float charge is 324V) 24 jars of 12V VRLA

 

 

Number of Lead-Acid Cells

144 = [24 x 6 cell (12V) blocks], nominal

 

 

 

 

 

 

 

 

 

 

 

 

Float Voltage

2.25V/cell, selectable from 2.2 - 2.3V/cell

 

 

 

 

 

Constant current and constant voltage charge mode

 

 

 

 

 

 

 

 

 

Temperature Compensation

-3.0mV/°C, selectable from 0 to -5.0mV/°C around 77°F (25°C) or 86°F (30°C) or inhibit

Ripple Voltage

1%

 

 

 

 

 

 

Ripple Current, ~ C10

5%

 

 

 

 

 

 

Boost Charge

2.35 V/cell (selectable from 2.30-2.40V/cell)

 

 

 

 

 

Voltage

Constant current and constant voltage charge mode

 

 

 

 

 

Float-boost current trigger 0.050 C10 (selectable 0.030-0.070)

 

 

 

Boost Control

Boost-float current trigger 0.010 C10 (selectable 0.005-0.025)

 

 

 

 

24 hr safety time-out (selectable 8-30 hr)

 

 

 

 

 

 

Boost charge mode inhibit also selectable

 

 

 

 

 

 

1.63 V/cell (selectable from 1.60-1.750V/cell)

 

 

 

 

 

End of Discharge

Auto Inverse EOD voltage x discharge current mode

 

 

 

 

 

(The end of discharge voltage increases at low discharge currents)

 

 

 

2.4 V/cell (selectable from 2.3-2.4V/cell)

 

 

 

 

 

Battery Charge

Constant current and constant voltage charge mode

 

 

 

 

 

Programmable auto trigger or inhibit of boost mode

 

 

 

 

Battery Charging Power1

UPS (kVA)

15

30

45

60

75

90

 

 

 

 

 

 

 

Battery Charging Power (kW)

2.25

4.5

6.75

9

11.25

13.25

Max Current (Adjustable)2

Max Charging Current (A)

11

22

33

44

55

66

 

1.At low input voltage, the UPS recharge capability increases with load decrease (up to the maximum capacity indicated).

2.Maximum currents listed are for end of discharge voltage of 1.67 V/cell for 144 cells.

108

Page 118
Image 118
Emerson 115-600V, 115-120 Rectifier input Parameter 15-90kVA, Battery DC intermediate circuit, Parameter 15 90kVA, UPS kVA

115-600V, 115-208, 115-120, 115-50/60HZ, 115-480 specifications

The Emerson 15-90KVA series is a robust and versatile power solution designed for various applications including commercial, industrial, and data center operations. Operating at voltage ranging from 115 to 480 volts, and supporting frequencies of either 50 or 60 Hz, this series is engineered to meet diverse power requirements.

One of the standout features of the Emerson 15-90KVA is its exceptional reliability and performance under varying load conditions. This power system incorporates cutting-edge technologies that enhance operational efficiency while minimizing downtime. The robust design of the system enables it to maintain optimal performance even in harsh environmental conditions, providing power continuity and safeguarding critical operations.

The Emerson 15-90KVA is equipped with advanced protection mechanisms that ensure the safety of connected equipment. These include overload protection, short-circuit protection, and thermal protection systems, which work together to prevent potential damage from power surges or faults. Moreover, the unit features a user-friendly interface that facilitates easy monitoring and control, enabling operators to track performance metrics and manage power supply effectively.

Another significant characteristic of this power series is its modular design, allowing for scalability and flexibility. Users can easily add or remove capacity based on changing power demands without the need for extensive system overhauls. This scalability makes the Emerson 15-90KVA ideal for growing businesses that require adaptable power solutions.

Energy efficiency is a focal point for the Emerson power series. Utilizing advanced power electronics and intelligent control algorithms, the system minimizes energy losses, ensuring that more power is available for direct usage. This not only reduces operational costs but also aligns with growing sustainability initiatives by lowering the overall carbon footprint.

In summary, the Emerson 15-90KVA series is a high-performance power solution characterized by its reliability, advanced protection features, modular scalability, and energy efficiency. Its versatility across multiple voltage levels and frequency options makes it suitable for a wide range of applications, solidifying its position as a preferred choice in the industry. Whether for industrial facilities, data centers, or commercial spaces, the Emerson 15-90KVA is designed to meet and exceed power demands effectively and efficiently.