Emerson 15-90KVA, 115-120, 115-208, 115-50/60HZ, 115-600V Static Bypass Assembly, LED indications

Models: 115-600V 115-208 115-120 115-50/60HZ 115-480 15-90KVA

1 132
Download 132 pages 53.17 Kb
Page 25
Image 25

Installation

The Fault LED will illuminate red when the Liebert FlexPower assembly has a problem.

Table 4

LED indications

 

 

 

LED Status

 

Indication

Run LED (Green)

 

 

Flashing Green

 

The inverter is starting, but has no output yet.

Constant Green

 

The inverter has started to supply power.

OFF

 

 

The inverter has not started up.

Fault LED (Red)

 

 

 

 

 

Auxiliary power failure (15V or 24V), rectifier overtemperature, rectifier failure (including battery

 

 

 

SCR short circuit), battery converter failure, soft start failure, main circuit back feed, abnormal

Constant Red

 

input current, inverter failure, output short circuit, bypass SCR short circuit fault, inverter relay

 

 

 

short circuit fault, abnormal bus voltage under non-sleep mode, module not ready, module ID

 

 

 

out of range and duplicated module ID.

 

 

 

Charger failure, abnormal main circuit voltage, abnormal main circuit frequency, main circuit

Flashing Red

 

undervoltage, main circuit reverse phase, battery unavailable, reverse battery, input zero-loss,

 

current sharing failure, module overload, inverter relay disconnection fault, bypass SCR

 

 

 

 

 

 

disconnection fault and input fuse blown.

 

 

 

 

OFF

 

 

No above failures or alarms.

 

 

 

 

2.9Static Bypass Assembly

Figure 3 Static bypass assembly connections

J5

J4

J7

J8

J10

J11

J6

J9

J12

 

Liebert IntelliSlot

 

 

Monitor RS-485 RS-232

 

Bays 1, 2, 3

The Static bypass assembly has three Liebert IntelliSlot interface card bays and connections for ancillary cabinets (Liebert BDC and battery) and for options.

15

Page 25
Image 25
Emerson 15-90KVA, 115-120, 115-208, 115-50/60HZ, 115-600V, 115-480 user manual Static Bypass Assembly, LED indications