Maintenance

Table 57 UPS status messages (continued)

Event Message

Description / Suggested Action (if any)

 

 

DC Bus Abnormal

Shut off inverter due to abnormal DC bus voltage.

Contact Liebert Services at 800-543-2378 for assistance.

 

System Transfer

The whole paralleled UPS system transferred to bypass at the same time. This message will

appear on the UPS which passive transfer to bypass.

 

 

Rectifier, inverter and battery converter were shutdown because DC bus voltage is too high.

DC Bus Overvoltage

Check whether there is a fault in rectifier side. If no, then check whether overload occurs.

Restart the inverter after resetting the fault. If fault does not clear, contact Liebert Services at 800-

 

 

543-2378 for assistance.

LBS Active

The LBS setting is active. The UPS is acting as an LBS master or slave in a dual bus

configuration.

 

Battery ground fault

Battery ground fault from dry contact signal. Contact Liebert Services at 800-543-2378 for

assistance.

 

Inverter turned On

Manual Turn On via front panel

manually

 

Inverter turned Off

Manual Turn Off via front panel

manually

 

EPO

Emergency Power Off

Transfer Confirm

Interrupted Transfer Confirm

 

 

Transfer Cancel

Interrupted Transfer is cancel

 

 

Unit Off Confirm

Unit Turned Off Confirm

System Off Confirm

System Turned Off Confirm

 

 

Fault Reset

Fault Reset

 

 

Alarm Silence

Alarm Silence

Turn On Fail

Turn On Fail

 

 

Alarm Reset

Audible Alarm Reset

 

 

Bypass Mode

UPS in Bypass Mode

Normal Mode

UPS in Normal Mode

 

 

Battery Mode

UPS in Battery Mode

 

 

Output Disabled

UPS Output Disabled

Maint. Disconnect Closed

Maintenance Disconnect Closed

 

 

Reserved

 

 

 

Output Disconnect Open

Output Disconnect Open

Battery Reverse

Connect the battery again and check the wiring of batteries.

 

 

No Battery

Check the battery and the wiring of batteries.

 

 

Auto start

After UPS was shutdown at EOD, inverter auto starts when utility is restored.

BCB closed

BCB closed from dry contact signal.

 

 

BCB open

BCB open from dry contact signal.

 

 

Battery Float Charging

Battery is float charging.

Battery Boost Charging

Battery is boost charging.

 

 

Battery Discharging

Battery is discharging.

 

 

Battery Period Testing

Battery is period self-testing.

Batt. Capacity Testing

Battery is capacity self-testing.

 

 

Batt. Maint. Testing

Battery is maintenance self-testing.

 

 

Inverter in Setting

Inverter is in parameter setting.

Rectifier in Setting

Rectifier is in parameter setting.

 

 

Batt. Converter Fault

Battery converter output voltage beyond limits or battery fuse failed. Battery converter shuts

down. Battery backup not available.

 

Operation Invalid

This record is registered following an incorrect operation.

 

 

119

Page 129
Image 129
Emerson 115-50/60HZ, 115-120, 15-90KVA, 115-208, 115-600V, 115-480 user manual 119

115-600V, 115-208, 115-120, 115-50/60HZ, 115-480 specifications

The Emerson 15-90KVA series is a robust and versatile power solution designed for various applications including commercial, industrial, and data center operations. Operating at voltage ranging from 115 to 480 volts, and supporting frequencies of either 50 or 60 Hz, this series is engineered to meet diverse power requirements.

One of the standout features of the Emerson 15-90KVA is its exceptional reliability and performance under varying load conditions. This power system incorporates cutting-edge technologies that enhance operational efficiency while minimizing downtime. The robust design of the system enables it to maintain optimal performance even in harsh environmental conditions, providing power continuity and safeguarding critical operations.

The Emerson 15-90KVA is equipped with advanced protection mechanisms that ensure the safety of connected equipment. These include overload protection, short-circuit protection, and thermal protection systems, which work together to prevent potential damage from power surges or faults. Moreover, the unit features a user-friendly interface that facilitates easy monitoring and control, enabling operators to track performance metrics and manage power supply effectively.

Another significant characteristic of this power series is its modular design, allowing for scalability and flexibility. Users can easily add or remove capacity based on changing power demands without the need for extensive system overhauls. This scalability makes the Emerson 15-90KVA ideal for growing businesses that require adaptable power solutions.

Energy efficiency is a focal point for the Emerson power series. Utilizing advanced power electronics and intelligent control algorithms, the system minimizes energy losses, ensuring that more power is available for direct usage. This not only reduces operational costs but also aligns with growing sustainability initiatives by lowering the overall carbon footprint.

In summary, the Emerson 15-90KVA series is a high-performance power solution characterized by its reliability, advanced protection features, modular scalability, and energy efficiency. Its versatility across multiple voltage levels and frequency options makes it suitable for a wide range of applications, solidifying its position as a preferred choice in the industry. Whether for industrial facilities, data centers, or commercial spaces, the Emerson 15-90KVA is designed to meet and exceed power demands effectively and efficiently.