Specifications and Technical Data

11.4UPS Electrical Characteristics

Refer to additional circuit breaker notes in 3.2.7 - Accessory Fuses and Backfeed Breaker Wiring.

NOTE

The breakers and cables used must be in accordance with NEC ANSI/NFPA 70. A disconnect breaker must be provided for AC input, DC input and AC output. Recommended cable sizes are suitable for operation at a maximum temperature of 86°F (30°C). For continuous operation at temperatures above 86°F (30°C), the site design should include cables that meet requirements for 104°F (40°C) installations.

Table 41 UPS currents and terminals—Input (for single-input unit, 208V operation)

 

 

 

 

 

Maximum Recommended Lug (T&B)

 

 

 

 

 

 

 

 

 

 

Nominal

Maximum

OCP

 

 

 

Compression

Mechanical

Unit

Input

Input

Device

 

75°C Wire

 

Lug Two Hole

Lug Two Hole

Rating

Current

Current

Rating

Bolt Size

Current, tot

Wire

3/8" Bolt

3/8" Bolt

15

44

55

70

M10 (3/8")

130

(1) #1

54857BE

32209

 

 

 

 

 

 

 

 

 

30

89

111

150

M10 (3/8")

150

(1) 1/0

54860BE

32209

 

 

 

 

 

 

 

 

 

45

133

166

200

M10 (3/8")

200

(1) 3/0

54864BE

32211

 

 

 

 

 

 

 

 

 

60

177

221

300

M10 (3/8")

300

(2) 1/0

54860BE

32209

 

 

 

 

 

 

 

 

 

75

221

276

350

M10 (3/8")

350

(2) 2/0

54862BE

32209

 

 

 

 

 

 

 

 

 

90

266

332

400

M10 (3/8")

460

(2) 4/0

54866BE

32211

 

 

 

 

 

 

 

 

 

Table 42 UPS currents and terminals—Input (for dual-input unit only, 208V operation)

 

 

 

 

 

Maximum Recommended Lug (T&B)

 

 

 

 

 

 

 

 

 

 

Nominal

Maximum

OCP

 

 

 

Compression

Mechanical

Unit

Input

Input

Device

 

75°C Wire

 

Lug Two Hole

Lug Two Hole

Rating

Current

Current

Rating

Bolt Size

Current, tot

Wire

3/8" Bolt

3/8" Bolt

15

44

55

70

M10 (3/8")

130

(1) #1

54857BE

32209

 

 

 

 

 

 

 

 

 

30

89

111

150

M10 (3/8")

150

(1) 1/0

54860BE

32209

 

 

 

 

 

 

 

 

 

45

133

166

200

M10 (3/8")

200

(1) 3/0

54864BE

32211

 

 

 

 

 

 

 

 

 

60

177

221

300

M10 (3/8")

300

(2) 1/0

54860BE

32209

 

 

 

 

 

 

 

 

 

75

221

276

350

M10 (3/8")

350

(2) 2/0

54862BE

32209

 

 

 

 

 

 

 

 

 

90

266

332

400

M10 (3/8")

460

(2) 4/0

54866BE

32211

 

 

 

 

 

 

 

 

 

Table 43 UPS currents and terminals—Bypass input (for dual-input units, 208V operation)

 

 

 

 

 

 

Maximum Recommended Lug (T&B)

 

 

 

 

 

 

 

 

 

Nominal

 

 

 

 

Compression

Mechanical

Unit

Input

OCP Device

 

75°C Wire

 

Lug Two Hole

Lug Two Hole

Rating

Current

Rating

Bolt Size

Current, tot

Wire

3/8" Bolt

3/8" Bolt

15

42

70

M10 (3/8")

130

(1) #1

54857BE

32209

 

 

 

 

 

 

 

 

30

83

125

M10 (3/8")

150

(1) 1/0

54860BE

32209

 

 

 

 

 

 

 

 

45

125

200

M10 (3/8")

175

(1) 2/0

54862BE

32209

 

 

 

 

 

 

 

 

60

167

250

M10 (3/8")

230

(1) 4/0

54866BE

32211

 

 

 

 

 

 

 

 

75

208

350

M10 (3/8")

300

(2) 1/0

54860BE

32209

 

 

 

 

 

 

 

 

90

250

400

M10 (3/8")

350

(2) 2/0

54862BE

32209

 

 

 

 

 

 

 

 

106

Page 116
Image 116
Emerson 115-208, 115-120, 15-90KVA, 115-50/60HZ UPS Electrical Characteristics, Maximum Recommended Lug T&B, Nominal Maximum

115-600V, 115-208, 115-120, 115-50/60HZ, 115-480 specifications

The Emerson 15-90KVA series is a robust and versatile power solution designed for various applications including commercial, industrial, and data center operations. Operating at voltage ranging from 115 to 480 volts, and supporting frequencies of either 50 or 60 Hz, this series is engineered to meet diverse power requirements.

One of the standout features of the Emerson 15-90KVA is its exceptional reliability and performance under varying load conditions. This power system incorporates cutting-edge technologies that enhance operational efficiency while minimizing downtime. The robust design of the system enables it to maintain optimal performance even in harsh environmental conditions, providing power continuity and safeguarding critical operations.

The Emerson 15-90KVA is equipped with advanced protection mechanisms that ensure the safety of connected equipment. These include overload protection, short-circuit protection, and thermal protection systems, which work together to prevent potential damage from power surges or faults. Moreover, the unit features a user-friendly interface that facilitates easy monitoring and control, enabling operators to track performance metrics and manage power supply effectively.

Another significant characteristic of this power series is its modular design, allowing for scalability and flexibility. Users can easily add or remove capacity based on changing power demands without the need for extensive system overhauls. This scalability makes the Emerson 15-90KVA ideal for growing businesses that require adaptable power solutions.

Energy efficiency is a focal point for the Emerson power series. Utilizing advanced power electronics and intelligent control algorithms, the system minimizes energy losses, ensuring that more power is available for direct usage. This not only reduces operational costs but also aligns with growing sustainability initiatives by lowering the overall carbon footprint.

In summary, the Emerson 15-90KVA series is a high-performance power solution characterized by its reliability, advanced protection features, modular scalability, and energy efficiency. Its versatility across multiple voltage levels and frequency options makes it suitable for a wide range of applications, solidifying its position as a preferred choice in the industry. Whether for industrial facilities, data centers, or commercial spaces, the Emerson 15-90KVA is designed to meet and exceed power demands effectively and efficiently.